![ABB ACS320 series Скачать руководство пользователя страница 89](http://html.mh-extra.com/html/abb/acs320-series/acs320-series_user-manual_2965089.webp)
Application macros 89
PFA control macro
This macro provides parameter settings for pump and fan alternation (PFA)
applications. To enable the macro, set the value of parameter
to 7 (PUMP ALTERNA).
Note:
Parameter
must remain in the default setting 0 (OFF).
Parameters changed relative to HVAC default
Parameter
Value
Parameter
Value
9902
APPLIC MACRO
7 (PUMP ALTERNA)
2203
DECELER TIME 1
10.0 s
1201
CONST SPEED SEL
0 (NOT SEL)
8109
START FREQ 1
58.0 Hz
1401
RELAY OUTPUT 1
31 (PFA)
8110
START FREQ 2
58.0 Hz
1608
START ENABLE 1
0 (NOT SEL)
8111
START FREQ 3
58.0 Hz
2101
START FUNCTION
1 (AUTO)
8120
INTERLOCKS
2202
ACCELER TIME 1
10.0 s
8123
PFA ENABLE
1 (ACTIVE)
X1A
1
SCR
Signal cable shield (screen)
2
AI1
Ext. ref. 1 (Hand) / Ext. ref. 2 (PID/PFC)
: 0…10 V
3
GND
Analog input circuit common
4
+10V
Reference voltage: +10 V DC, max. 10 mA
5
AI2
Process actual value
: 4…20 mA
6
GND
Analog input circuit common
7
AO
Output frequency value
: 0…20 mA
8
GND
Analog output circuit common
9
+24V
Auxiliary voltage output: +24 V DC, max. 200 mA
10 GND
Auxiliary voltage output common
11 DCOM
Digital input common
12 DI1
Stop (0) / Start (1) (Hand)
13 DI2
Hand (0) / PID/PFC (1) control selection
14 DI3
Interlock:
Deactivation always stops the drive
15 DI4
Interlock:
Deactivation stops constant speed motor
16 DI5
Stop (0) / Start (1) (PID/PFC)
X1B
17 ROCOM
Relay output 1
PFC
18 RONC
19 RONO
20 DOSRC
Digital output, max. 100 mA
No fault [Fault (-1)]
21 DOOUT
22 DOGND
1…10 kohm
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...