![ABB ACS320 series Скачать руководство пользователя страница 395](http://html.mh-extra.com/html/abb/acs320-series/acs320-series_user-manual_2965395.webp)
Technical data 395
Electric power network specification
Voltage (
U
1
)
200/208/220/230/240 V AC 1-phase for 200 V AC drives
200/208/220/230/240 V AC 3-phase
for 200 V AC drives
380/400/415/440/460/480 V AC 3-phase for 400 V AC drives
±10% variation from converter nominal voltage is allowed as default.
Short-circuit capacity
Maximum allowed prospective short-circuit current at the input power
connection as defined in IEC 60439-1 is 100 kA. The drive is suitable
for use in a circuit capable of delivering not more than 100 kA rms
symmetrical amperes at the drive maximum rated voltage.
Note
: Use appropriate fuses or MMP’s to achieve 100 kA.
Frequency
50/60 Hz ± 5%, maximum rate of change 17%/s
Imbalance
Max.
±3% of nominal phase to phase input voltage
Motor connection data
Voltage (
U
2
)
0 to
U
1
,
3-phase symmetrical,
U
max
at the field weakening point
Short-circuit protection
(IEC 61800-5-1,
UL 508C)
The motor output is short-circuit proof by IEC 61800-5-1 and
UL 508C.
Frequency
0…500 Hz
Frequency resolution
0.01 Hz
Current
See section
or
.
Power limit
1.5 ·
P
N
Field weakening point
10…500 Hz
Switching frequency
4, 8, 12 or 16 kHz
Maximum
recommended
motor cable length
R0: 30 m (100 ft), R1…R4: 50 m (165 ft)
With output chokes the motor cable length may be extended to 60 m
(195 ft) for R0 and 100 m (330 ft) for R1…R4.
To comply with the European EMC Directive, use the cable lengths
specified in the table below for 4 kHz switching frequency. The
lengths are given for using the drive with the internal EMC filter or an
optional external EMC filter.
4 kHz switching
frequency
Internal EMC filter Optional external
EMC filter
Second environment
(category C3
1)
)
30 m (100 ft)
30 m (100 ft)
minimum
First environment
(category C2
1)
)
-
30 m (100 ft)
1)
See the new terms in section
.
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...