![ABB ACS320 series Скачать руководство пользователя страница 344](http://html.mh-extra.com/html/abb/acs320-series/acs320-series_user-manual_2965344.webp)
344 Fieldbus control
Except where restricted by the drive, all parameters are available for both reading
and writing. The parameter writes are verified for the correct value, and for a valid
register addresses.
Note:
Parameter writes through standard Modbus are always volatile, in other words,
modified values are not automatically stored to permanent memory. Use parameter
to save all altered values.
The drive supports the following Modbus function codes for 4xxxx registers:
Actual values
The contents of the register addresses 40005…40012 are actual values and are:
• Specified using parameters 5310…5317.
• Read-only values containing information on the operation of the drive.
• 16-bit words containing a sign bit and a 15-bit integer.
• When negative values, written as the two’s complement of the corresponding
positive value.
• Scaled as described earlier in
.
Exception codes
Exception codes are serial communication responses from the drive.
The drive
supports the standard Modbus exception codes defined below.
5331
MDB DATA OUT 9
Specifies the parameter mapped to Modbus register 40088.
5332
MDB DATA OUT 10
Specifies the parameter mapped to Modbus register 40089.
Function Code
Description
03
Read holding 4xxxx registers
06
Preset single 4xxxx register
16 (0x10 Hex)
Preset multiple 4xxxx registers
23 (0x17 Hex)
Read/write 4xxxx registers
Exception
Code
Meaning
01
Unsupported command
02
The data address received in the query is not allowable. It is not a defined
parameter/group.
03
A value contained in the query data field is not an allowable value for the drive,
because it is one of the following:
Outside min. or max. limits.
Parameter is read-only.
Message is too long.
Parameter write not allowed when start is active.
Parameter write not allowed when factory macro is selected.
Code
Description
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...