![ABB ACS320 series Скачать руководство пользователя страница 326](http://html.mh-extra.com/html/abb/acs320-series/acs320-series_user-manual_2965326.webp)
326 Fieldbus control
Binary value object instance summary
The following table summarizes the Binary value objects supported:
Instance
ID
Object Name
Description
Active/Inactive
Text
Present Value
Access Type
BV0
RUN/STOP ACT Indicates the Run status of
the drive, regardless of the
control source.
RUN/STOP
R
BV1
FWD/REV ACT
Indicates the rotation
direction of the motor,
regardless of control source.
REV/FWD
R
BV2
FAULT ACT
Indicates the fault status of
the drive.
FAULT/OK
R
BV3
EXT 1/2 ACT
Indicates which control
source is active: External 1
or External 2.
EXT2/EXT1
R
BV4
HAND/AUTO
ACT
Indicates which control
mode the drive is in: Hand
or Auto.
HAND/AUTO
R
BV5
ALARM ACT
Indicates the alarm status of
the drive.
ALARM/OK
R
BV6
MAINT REQ
Indicates the maintenance
status of the drive.
MAINT/OK
R
BV7
DRIVE READY
Indicates whether the drive
is ready to accept a run
command.
READY/NOT
READY
R
BV8
AT SETPOINT
Indicates whether the drive
is at the commanded
setpoint.
YES/NO
R
BV9
RUN ENA ACT
Indicates the Run Enable
command status, regardless
of the control source.
ENABLE/DISABLE R
BV10
RUN/STOP CMD Command to start the drive
(drive must be configured
for BACnet control).
RUN/STOP
C
BV11
FWD/REV CMD
Command to change the
rotational direction of motor
(drive must be configured
for BACnet control).
REV/FWD
C
BV12
RUN ENA CMD
Command to assert Run
Enable (drive must be
configured for BACnet
control).
ENABLE/DISABLE C
BV13
EXT 1/2 CMD
Command to select
External 1 or External 2 as
the active control source
(drive must be configured
for BACnet control).
EXT2/EXT1
C
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...