288 Fieldbus control
Communication set-up – EFB
Serial communication selection
To activate the serial communication, set parameter
• 1 (
STD
MODBUS
)
• 2 (
N
2)
• 3 (
FLN
)
• 5 (
BACNET
).
Note:
If you cannot see the desired selection on the panel, your drive does not have
that protocol software in the application memory.
Serial communication configuration
automatically sets the appropriate default
values in parameters that define the communication process. These parameters and
descriptions are defined below. In particular, note that the station Id may require
adjustment.
Code Description
EFB Protocol Reference
Modbus
N2
FLN
BACnet
Contains the identification
and program revision of
the protocol.
Do not edit. Any non-zero value entered for parameter
, sets this parameter automatically. The
format is: XXYY, where xx = protocol ID, and YY = program
revision.
Defines the node address
of the EIA-485 link.
Set each drive on the network
with a unique value for this
parameter.
When this protocol is selected,
the default value for this
parameter is: 1
Note:
For a new address to take
affect, the drive power must be
cycled
OR
5302 must first be set
to 0 before selecting a new
address. Leaving 5302 = 0
places the EIA-485 channel in
reset, disabling communication.
Sets MS/TP MAC ID. A
temporary value of 0
places the protocol
channel in reset.
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...