![ABB ACS320 series Скачать руководство пользователя страница 217](http://html.mh-extra.com/html/abb/acs320-series/acs320-series_user-manual_2965217.webp)
Actual signals and parameters 217
Group 35: Motor temp meas
Group 35: Motor temp meas
Code
Description
Range
Resolution
Default
S
3501
SENSOR TYPE
0…6
1
0
Activates the motor temperature measurement function and selects the sensor type.
See also parameter
0 = NONE – Function is inactive.
1 = 1 x PT100 – Function is active. The temperature is measured with one Pt100
sensor. Analog output AO feeds constant current through the sensor. The sensor
resistance increases as the motor temperature rises, as does the voltage over the
sensor. The temperature measurement function reads the voltage through analog
input AI1/2 and converts it to degrees centigrade.
2 = 2 x PT100 – Function is active. The temperature is measured using two Pt100
sensors. See selection 1 x PT100 above.
3 = 3 x PT100 – Function is active. The temperature is measured using three Pt100
sensors. See selection 1 x PT100 above.
4 = PTC – Function is active. The
temperature is supervised using one
PTC sensor. Analog output AO feeds
constant current through the sensor. The
resistance of the sensor increases
sharply as the motor temperature rises
over the PTC reference temperature
(Tref), as does the voltage over the
resistor. The temperature measurement
function reads the voltage through
analog input AI1/2 and converts it into
ohms. The figure on the right-hand side
shows typical PTC sensor resistance
values as a function of the motor
operating temperature.
5 = THERM (0) – Function is active. The motor temperature is monitored using a PTC
sensor (see selection PTC) connected to a drive through a normally closed
thermistor relay connected to a digital input. 0 = motor overtemperature.
6 = THERM (1) – Function is active. The motor temperature is monitored using a PTC
sensor (see selection PTC) connected to a drive through a normally open
thermistor relay connected to a digital input. 1 = motor overtemperature.
See the figures in section
Motor temperature measurement through the standard I/O
100
550
1330
4000
Ohm
T
Temperature
Resistance
Normal
0 … 1.5 kohm
Excessive
> 4 kohm
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...