136 Program features
Load analyzer
The load analyzer can be used for analyzing the customer’s process and sizing the
drive and the motor.
Peak value logger
The user can select a signal (
) to be monitored by the peak
value logger (PVL). The signal is sampled at 2 ms intervals when the drive is running.
The logger records the peak (maximum) value of the signal along with the time the
peak occurred, as well as output current, DC voltage and output frequency at the time
of the peak.
Amplitude loggers
The drive has two amplitude loggers.
For amplitude logger 2 (AL2), the user can select a signal (
to be sampled at 200 ms intervals when the drive is running, and specify a value that
corresponds to 100%. The collected samples are sorted into 10 read-only parameters
according to their amplitude. Each parameter represents an amplitude range 10
percentage points wide, and displays the percentage of the collected samples that fall
within that range.
Amplitude logger 1 (AL1) is fixed to monitor output current, and it cannot be reset.
With amplitude logger 1, 100% corresponds to the nominal output current of the drive
(
I
2N
).
The peak value logger and amplitude logger 2 can be reset by a user-defined
method. They are also reset if either of the signals or the peak value filter time is
changed.
P
er
cen
ta
ge
of
sa
mpl
e
s
0…
10
%
10
…
2
0%
20
…
3
0%
30
…
4
0%
40
…
5
0%
50
…
6
0%
60
…
7
0%
70
…
8
0%
80
…
9
0%
>9
0%
Amplitude ranges (parameters
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...