Technical data 341
Fuses and MMPs
Type
Fuses
MMPs
ACS310-
gG
UL Class T or
CC (600 V)
Frame
I
1N
MMP Type E
3,4)
Min. Encl.
Vol.
6)
x = E/U
1)
A
min A
2)
max A
A
dm
3
in
3
1-phase
U
N
= 200…240 V
(200, 208, 220, 230, 240 V)
01x-02A4-2
10
6
10
R0
6.1
MS132-6.3 & S1-M3-25
5)
18.9
1152
01x-04A7-2
16
10
20
R1
11.4
MS451-16E
18.9
1152
01x-06A7-2
16
15
25
R1
16.1
MS451-20E
18.9
1152
01x-07A5-2
20
15
30
R2
16.8
MS451-20E
-
-
01x-09A8-2
25
15
35
R2
21.0
MS451-25E
-
-
3-phase
U
N
= 200
…
240 V
(200, 208, 220, 230, 240 V)
03x-02A6-2
10
3
10
R0
4.7
MS132-6.3 & S1-M3-25
5)
18.9
1152
03x-03A9-2
10
6
10
R0
6.7
MS132-10 & S1-M3-25
5)
18.9
1152
03x-05A2-2
10
6
15
R1
8.4
MS132-10 & S1-M3-25
5)
18.9
1152
03x-07A4-2
16
10
15
R1
13.0
MS451-16E
18.9
1152
03x-08A3-2
16
10
15
R1
13.2
MS451-16E
18.9
1152
03x-10A8-2
16
15
20
R2
15.7
MS451-20E
-
-
03x-14A6-2
25
15
30
R2
23.9
MS451-25E
-
-
03x-19A4-2
25
20
35
R2
27.3
MS451-32E
-
-
03x-26A8-2
63
30
60
R3
45.0
MS451-50E
-
-
03x-34A1-2
80
35
80
R4
55.0
MS495-63E
-
-
03x-50A8-2 100
50
100
R4
76.0
MS495-90E
-
-
3-phase
U
N
= 380
…
480 V
(380, 400, 415, 440, 460, 480 V) (MMP ratings for 480Y/277V only)
03x-01A3-4
10
2
10
R0
2.0
MS132-2.5 & S1-M3-25
5)
18.9
1152
03x-02A1-4
10
2
10
R0
3.3
MS132-4.0 & S1-M3-25
5)
18.9
1152
03x-02A6-4
10
3
10
R1
3.8
MS132-6.3 & S1-M3-25
5)
18.9
1152
03x-03A6-4
10
3
10
R1
5.5
MS132-6.3 & S1-M3-25
5)
18.9
1152
03x-04A5-4
16
6
15
R1
6.3
MS132-10 & S1-M3-25
5)
18.9
1152
03x-06A2-4
16
6
15
R1
8.8
MS132-10 & S1-M3-25
5)
18.9
1152
03x-08A0-4
16
6
20
R1
11.0
MS451-16E
18.9
1152
03x-09A7-4
20
10
25
R1
12.0
MS451-16E
18.9
1152
03x-13A8-4
25
10
30
R3
17.0
MS451-20E
-
-
03x-17A2-4
35
15
35
R3
20.0
MS451-25E
-
-
03x-25A4-4
50
20
50
R3
28.0
MS451-32E
-
-
03x-34A1-4
80
25
80
R4
48.0
MS451-50E
-
-
03x-41A8-4 100
30
100
R4
56.0
MS495-63E
-
-
03x-48A4-4 100
35
100
R4
61.0
MS495-63E
-
-
00578903.xls.J
1)
E = EMC filter connected (metal EMC filter screw installed),
U = EMC filter disconnected (plastic EMC filter screw installed), U.S parameterization.
2)
minimum fuse size can be used with input choke according to table in Rating section
3)
All manual motor protections listed are type E self-protected up to 65kA.
See ABB publication AC1010 for complete technical data on ABB type E manual motor protectors
4)
Manual motor protectors may require adjusting the trip limit from the factory setting at or above the drive
input. Amps to avoid nuisance tripping. If the manual motor protector is set to the maximum current trip level
and nuisance tripping is occurring, then select the next size MMP. (MS132-10 is the highest size in MS132
frame size to meet type E at 65kA, the next size up is the MS451-16E)