Program features 145
Settings
Diagnostics
Motor temperature measurement through the standard I/O
This section describes the temperature measurement of one motor when the drive
I/O terminals are used as the connection interface.
Motor temperature can be measured using Pt100 or PTC sensors connected to
analog input and output.
WARNING!
According to IEC 664, the connection of the motor temperature
sensor requires double or reinforced insulation between motor live parts and
the sensor. Reinforced insulation entails a clearance and creepage distance of 8 mm
(400/500 V AC equipment).
If the assembly does not fulfill the requirement, the I/O board terminals must be
protected against contact and they may not be connected to other equipment, or the
temperature sensor must be isolated from the I/O terminals.
Parameter
Additional information
PID control activation
Sleep function settings
Parameter
Additional information
PID sleep function status through RO 1
PID sleep function status through RO 2…4. With option
MREL-01 only.
Alarm
Additional information
Sleep mode
T
T
T
T
3.3 nF
AI1
GND
AO
GND
AI1
GND
AO
GND
Motor
Motor
One sensor
Three sensors
3.3 nF