354
Fieldbus control through the embedded fieldbus interface (EFB)
The new settings will take effect when the drive is powered up the next time, or
when they are validated by parameter
).
Setting the drive control parameters
After the embedded fieldbus interface has been set up, check and adjust the
drive control parameters listed in the table below. The
Setting for fieldbus
control
column gives the value or values to use when the embedded fieldbus
signal is the desired source or destination for that particular drive control
signal. The
Function/Information
column gives a description of the parameter.
…
…
For example, the
default settings
(I/Os 1…6
contain the
control word, the
status word, two
references and
two actual
values)
Defines the address of the drive parameter
which the Modbus master accesses when
it reads from or writes to the register
address corresponding to Modbus In/Out
parameters. Select the parameters that
you want to read or write through the
Modbus I/O words.
,
,
These settings write the incoming data
into storage parameters
or
Validates the settings of the configuration
parameters.
Parameter
Setting for
fieldbus control
Function/Information
CONTROL COMMAND SOURCE SELECTION
Selects fieldbus as the source for the start
and stop commands when EXT1 is selected
as the active control location.
Selects fieldbus as the source for the start
and stop commands when EXT2 is
selected as the active control location.
SPEED REFERENCE SELECTION
Selects a reference received through the
embedded fieldbus interface as speed
reference 1.
Parameter
Setting for
fieldbus control
Function/Information
Содержание ACS280
Страница 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Страница 4: ......
Страница 10: ...10 ...
Страница 16: ...16 Control panel ...
Страница 20: ...20 Start up ID run and use ...
Страница 24: ...24 Default control connection ...
Страница 88: ...88 Program features ...
Страница 298: ...298 Parameters ...