Fieldbus control through the embedded fieldbus interface (EFB)
System overview
The drive can be connected to an external control system through a
communication link using the embedded fieldbus interface.
Modbus
The embedded fieldbus interface supports the Modbus RTU protocol. The drive
control program can handle 10 Modbus registers in a 10-millisecond time level.
For example, if the drive receives a request to read 20 registers, it will start its
response within 22 ms of receiving the request – 20 ms for processing the
request and 2 ms overhead for handling the bus. The actual response time
depends on other factors as well, such as the baud rate (a parameter setting in
the drive).
The drive can be set to receive all of its control information through the fieldbus
interface, or the control can be distributed between the embedded fieldbus
interface and other available sources, for example, digital and analog inputs.
Setting up the embedded fieldbus interface (Modbus)
To take the Modbus into use, manually set the drive up for the embedded
fieldbus communication with the parameters shown in the table below. The
Setting for fieldbus control
column gives either the value to use or the default
value. The
Function/Information column
gives a description of the parameter.
Modbus parameter settings for embedded fieldbus interface
Parameter
Setting for
fieldbus control
Function/Information
COMMUNICATION INITIALIZATION
Initializes embedded fieldbus
communication.
EMBEDDED MODBUS CONFIGURATION
1 (default)
Node address. There must be no two
nodes with the same node address online.
(default)
Defines the communication speed of the
link. Use the same setting as in the master
station.
(default)
Selects the parity and stop bit setting. Use
the same setting as in the master station.
(default)
Defines the action taken when a
communication loss is detected.
Содержание ACS280
Страница 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Страница 4: ......
Страница 10: ...10 ...
Страница 16: ...16 Control panel ...
Страница 20: ...20 Start up ID run and use ...
Страница 24: ...24 Default control connection ...
Страница 88: ...88 Program features ...
Страница 298: ...298 Parameters ...