Fault tracing 343
5090 STO hardware failure STO hardware diagnostics
has detected hardware
failure.
Contact your local ABB representative
for hardware replacement.
5091
Safe torque off
Programmable fault:
Safe torque off function is
active, ie. safety circuit
signal(s) connected to
connector STO is broken
during start or run.
Check safety circuit connections. For
more information, see chapter
The
Safe torque off function
in the
hardware manual of the drive and
description of parameter
(page
).
5092
PU logic error
Power unit memory has
cleared.
Contact your local ABB representative.
5093
Rating ID mismatch
The hardware of the drive
does not match the
information stored in the
memory. This may occur eg.
after a firmware update.
Cycle the power to the drive. You may
have to be repeat this.
5094 Measurement circuit
temperature
Problem with internal
temperature measurement
of the drive.
Contact your local ABB representative.
5098
I/O communication
loss
Communication failure to
standard I/O.
Try resetting the fault or cycle the
power to the drive.
50A0 Fan
Cooling fan stuck or
disconnected.
Check fan operation and connection.
Replace fan if faulty.
5681
PU communication
Communication errors
detected between the drive
control unit and the power
unit.
Check the connection between the
drive control unit and the power unit.
5682
Power unit lost
Connection between the
drive control unit and the
power unit is lost.
Check the connection between the
control unit and the power unit.
5690
PU communication
internal
Internal communication
error.
Contact your local ABB representative.
5691
Measurement circuit
ADC
Measurement circuit fault.
Contact your local ABB representative.
5692
PU board powerfail
Power unit power supply
failure.
Contact your local ABB representative.
5693
Measurement circuit
DFF
Measurement circuit fault.
Contact your local ABB representative.
5696
PU state feedback
State feedback from output
phases does not match
control signals.
Contact your local ABB representative.
5697
Charging feedback
Charging feedback signal
missing.
Check the feedback signal coming
from the charging system.
6181
FPGA version
incompatible
Firmware and FPGA versions
are incompatible.
Reboot the control unit (using
parameter
)
or by cycling power. If the problem
persists, contact your local ABB
representative
Code
(hex) Fault / Aux. code
Cause
What to do
Содержание ACS280
Страница 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Страница 4: ......
Страница 10: ...10 ...
Страница 16: ...16 Control panel ...
Страница 20: ...20 Start up ID run and use ...
Страница 24: ...24 Default control connection ...
Страница 88: ...88 Program features ...
Страница 298: ...298 Parameters ...