Parameters 279
96.102 User lock functionality
(Visible when user lock is open)
Selects the actions or functionalities to be prevented
by the user lock. Note that the changes made take
effect only when the user lock is closed. See
parameter
.
0000h
0000h…FFFFh
Selection of actions to be prevented by user lock.
-
No.
Name/Value
Description
Default
FbEq 16
Bit
Name
Information
0
Disable ABB access
levels
1 = ABB access levels (service, advanced programmer, etc.; see
) disabled
1
Freeze parameter
lock state
1 = Changing the parameter lock state prevented, ie. pass code
358 has no effect
2
Disable file
download
1 = Loading of files to drive prevented. This applies to
• firmware upgrades
• parameter restore
• loading of adaptive or application programs
• changing home view of control panel
• editing drive texts
• editing the favorite parameters list on control panel
• configuration settings made through control panel such as
time/date formats and enabling/disabling clock display.
3
Disable FB write to
hidden
1 = Disable fieldbus write to closed access level.
4
Disable backups
1 = Disable backup file download.
5…10
Reserved
11
Disable OEM access
level 1
1 = Disable OEM access level 1.
12
Disable OEM access
level 2
1 = Disable OEM access level 2.
13
Disable OEM access
level 3
1 = Disable OEM access level 3.
14, 15
Reserved
Содержание ACS280
Страница 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Страница 4: ......
Страница 10: ...10 ...
Страница 16: ...16 Control panel ...
Страница 20: ...20 Start up ID run and use ...
Страница 24: ...24 Default control connection ...
Страница 88: ...88 Program features ...
Страница 298: ...298 Parameters ...