Parameters 215
Defines the temperature rise of the motor above
ambient when the motor is loaded with nominal
current. See the motor manufacturer's
recommendations.
The unit is selected by parameter
.
80 °C or
144 °F
0…300 °C or 0…540 °F
Temperature rise.
1 = 1°
Defines the thermal time constant for use with the
motor thermal protection model, defined as the time
to reach 63% of the nominal motor temperature. See
the motor manufacturer's recommendations.
256 s
100…10000 s
Motor thermal time constant.
1 = 1 s
Defines what action the drive should take when the
motor overload specified by parameter
occurs.
Warning and
fault
No.
Name/Value
Description
Default
FbEq 16
Motor nominal
temperature rise
Temperature
Time
Ambient temperature
100%
63%
100%
Time
Time
Motor thermal time
Motor current
Temperature rise