Parameters 211
KTY84 analog I/O
KTY84 sensor connected to the analog input selected
and an
analog output.
The following settings are required:
• Set the appropriate analog input unit selection
parameter in group
V
(volt).
• In parameter group
, set the source
selection parameter of the analog output to
The analog output feeds a constant current through
the sensor. As the resistance of the sensor increases
along with its temperature, the voltage over the
sensor increases. The voltage is read by the analog
input and converted into degrees.
2
1 x Pt100 analog I/O
Pt100 sensor connected to a standard analog input
selected by parameter
and an analog output.
The following settings are required:
• Set the hardware jumper or switch related to the
analog input to
U
(voltage). Any change must be
validated by a control unit reboot.
• Set the appropriate analog input unit selection
parameter in group
V
(volt).
• In parameter group
, set the source
selection parameter of the analog output to
The analog output feeds a constant current through
the sensor. As the resistance of the sensor increases
along with its temperature, the voltage over the
sensor increases. The voltage is read by the analog
input and converted into degrees.
5
2 x Pt100 analog I/O
, but with two
sensors connected in series. Using multiple sensors
improves measurement accuracy significantly.
6
3 x Pt100 analog I/O
, but with three
sensors connected in series. Using multiple sensors
improves measurement accuracy significantly.
7
Direct temperature
The temperature is taken from the source selected by
parameter
. The value of the source is assumed
to be in the unit of temperature specified by
parameter 96.16.
11
No.
Name/Value
Description
Default
FbEq 16
Содержание ACS280
Страница 1: ... ABB MACHINERY DRIVES ACS280 coldplate drives Firmware manual ...
Страница 4: ......
Страница 10: ...10 ...
Страница 16: ...16 Control panel ...
Страница 20: ...20 Start up ID run and use ...
Страница 24: ...24 Default control connection ...
Страница 88: ...88 Program features ...
Страница 298: ...298 Parameters ...