28 Control macros
Default control connections for the ABB standard macro
Terminals
Descriptions
Digital I/O connections
21 24 V
Aux. +24 V DC, max 200 mA
22 DGND
Aux. voltage output common
8
DI1
Stop (0) / Start (1)
9
DI2
Forward (0) / Reverse (1)
10 DI3
Constant speed selection
1)
11 DI4
Constant speed selection
1)
12 DCOM
Digital input common
18 DO
Running
19 DO COM
Digital output common
20 DO SRC
Digital output auxiliary voltage
Analog I/O
14 AI1/DI5
Speed reference (0…10V)
3)
13 AGND
Analog input circuit common
15 AI2
Not used
3)
16 AGND
Analog output circuit common
17 AO
Output frequency (0...20mA)
3)
23 10V
Ref. v10 V DC
24 SCREEN
Signal cable shield (screen)
Safe torque off (STO)
1
S+
Safe torque off function. Connected
at the factory. Drive starts only when
both circuits are closed.
2
SGND
3
S1
4
S2
Relay output
5
NC
No fault [Fault (-1)]
6
COM
7
NO
EIA-485 Modbus RTU
25 B+
Embedded Modbus RTU (EIA-485)
26 A-
27 AGND
28 SHIELD
Termination
NRKP
0D[RKP
2)