172 Parameters
Defines deceleration time 1 as the time required for the
speed to change from the speed defined by parameter
(
not
from parameter
) to zero.
If the speed reference decreases slower than the set
deceleration rate, the motor speed will follow the
reference.
If the reference changes faster than the set deceleration
rate, the motor speed will follow the deceleration rate.
If the deceleration rate is set too short, the drive will
automatically prolong the deceleration in order not to
exceed drive torque limits (or not to exceed a safe DC link
voltage). If there is any doubt about the deceleration time
being too short, ensure that DC overvoltage control is on
(parameter
Note:
If a short deceleration time is needed for a high
inertia application, the drive should be equipped with
braking equipment such as a brake chopper and brake
resistor.
3.000 s
0.000 …1800.000 s
Deceleration time 1.
10 = 1 s
Defines acceleration time 2. See parameter
60.000 s
0.000 …1800.000 s
Acceleration time 2.
10 = 1 s
Defines deceleration time 2. See parameter
60.000 s
0.000 …1800.000 s
Deceleration time 2.
10 = 1 s
Defines the acceleration time for the jogging function ie.
the time required for the speed to change from zero to the
speed value defined by parameter
See section
on page
.
60.000 s
0.000 …1800.000 s
Acceleration time for jogging.
10 = 1 s
Defines the deceleration time for the jogging function ie.
the time required for the speed to change from the speed
value defined by parameter
to zero.
See section
on page
.
60.000 s
0.000 …1800.000 s
Deceleration time for jogging.
10 = 1 s
No.
Name/Value
Description
Default
FbEq 16