65 kA when protected by fuses given in the fuse tables.
Rated conditional
short-circuit current
Icc(IEC 61800-5-1)
US and Canada: The drive is suitable for use on a circuit capable of
delivering not more than 100 kA symmetrical amperes (rms) at 480
V maximum when protected by fuses given in the fuse table. The
drive is also suitable for use on a circuit capable of delivering not
more than 65 kA symmetrical amperes (rms) at 480V maximum when
protected by the specific manual self-protected Type E combination
motor controllers given in the manual self-protected combination
motor controller table, provided the drive is mounted within an en-
closure of adequate minimum volume, and the assembly complies
with all applicable footnotes of the table.
Short-circuit current
protection
(UL 61800-5-1, CSA
C22.2 No. 274-13)
Use a mains choke if the network's line impedance is low (less than
0.3% total system impedance of all the ACS180 drives in the install-
ation), or has voltage imbalance, or harmonic distortion that make
the input current bigger than the nominal input current ratings. You
can use one choke for several drives as long as the choke current
rating is not exceeded.
Mains choke
47 to 63 Hz, maximum rate of change 17%/s
Frequency (f1)
Max. ±3% of nominal phase to phase input voltage
Imbalance
0.98 (at nominal load)
Fundamental power
factor (cos phi)
Motor connection data
Asynchronous induction motor or permanent magnet synchronous
motor
Motor type
0 to U1, 3-phase symmetrical, Umax at the field weakening point
Voltage (U2)
The motor output is short-circuit proof by IEC 61800-5-1 and UL
61800-5-1.
Short-circuit protec-
tion (IEC 61800-5-1,
UL 61800-5-1)
0…599 Hz
Frequency (f2)
0.01 Hz
Frequency resolution
See the rating information.
Current
4, 8, or 12 kHz
Switching frequency
■
Motor cable length
Operational functionality and motor cable length
The drive is designed to operate with optimum performance with the following
maximum motor cable lengths. The motor cable lengths may be extended with
output chokes as shown in the table.
130 Technical data
Содержание ACS180-04S-03A7-1
Страница 1: ...ABB MACHINERY DRIVES ACS180 drives Hardware manual...
Страница 2: ......
Страница 4: ......
Страница 12: ...12...
Страница 24: ...24...
Страница 83: ...Make sure that The motor and the driven equipment are ready for power up Installation checklist 83...
Страница 84: ...84...
Страница 96: ...96...
Страница 146: ...146...
Страница 148: ...Frame R0 148 Dimension drawings...
Страница 149: ...Frame R1 Dimension drawings 149...
Страница 151: ...Frame R3 Dimension drawings 151...
Страница 152: ...Frame R4 152 Dimension drawings...
Страница 160: ...160...
Страница 180: ...Declarations of conformity 180 The Safe torque off function...
Страница 181: ...The Safe torque off function 181...
Страница 182: ...182 The Safe torque off function...
Страница 183: ...The Safe torque off function 183...
Страница 184: ...184...
Страница 187: ...Installation 1 2 N m M4x16 2x 3 3 3 2 2 2 2 Accessories 187...
Страница 189: ...Installation 3 3 2 2 2 3 2 2 N m M4x16 4x 1 Accessories 189...