CDP CONTROL PANEL
PRODUCT
ACS1000W
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS213400 E01
REV.
J
LANG.
en
PAGE
137/166
10.4.2. Remote control
In remote control mode, operational commands or reference values come from a
higher-level control system via fieldbus or remote I/O.
However, with the following parameter settings it is possible to start and stop the
drive, to set the motor’s direction of rotation, and to enter reference values from
the CDP control panel.
–
11.01 EXT1 START/STOP/DIR = 10 (KEYPAD)
or
12.03 EXT REF1 SELECT = 1 (KEYPAD)
and
12.02 EXT1/EXT2 SELECT = 1 (EXT1)
–
11.02 EXT2 START/STOP/DIR 10 (KEYPAD)
or
12.06 EXT REF2 SELECT = 1 (KEYPAD)
and
12.02 EXT1/EXT2 SELECT = 2 (EXT2)
Entering remote control mode
–
To enter remote control, press the
LOC-REM
key.
Full remote control from a higher-level control system is indicated by a blank
space.
Partial remote control (some commands enabled locally) is indicated by the
letter
R
.
1
600.0 rpm 0
Status
Rdy to Strt
MotorSpeed 0.00
rpm
Power
0.0 %
LOC
REM
1 R
600.0 rpm 0
Status
Rdy to Strt
MotorSpeed 0.00
rpm
Power
0.0 %
LOC
REM