OPERATION
PRODUCT
ACS1000W
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS213400 E01
REV.
J
LANG.
en
PAGE
108/166
9.5. Local operator panel
Under normal operating conditions, the local operator panel allows you to operate
the drive without restrictions. For example, you can use the panel to perform the
following actions:
–
Connect and disconnect the main power supply
–
Set the reference value
–
Start and stop the drive
–
Display actual values, status messages, alarms and fault messages
–
View and setting parameters
–
Reset alarm and fault messages
–
Activate the emergency off circuit
For more information, see
.
Figure 9
-
1 Local operator panel
1) Control and data panel (CDP)
• Starts and stops the motor
• Displays status messages
• Displays alarm and fault messages of the drive and
monitored foreign equipment
• Resets alarm and fault messages
2)
OFF
illuminated push button
• Opens the main circuit breaker
3) ON illuminated push button
• Charges the DC link and closes the main circuit breaker
4)
GND SWITCH UNLOCKED
push button
• Lights up to indicate that the grounding switch of the
drive can be turned to the grounded or
ungrounded position
5)
EMERGENCY OFF
push button
• Prevents starting when pressed at standstill of
the drive
• Main circuit breaker opens immediately and DC link
discharges when pressed during operation of the drive
1
2
3
4
5