Fieldbus control
251
03.02 MAIN STATUS WORD
The upper case boldface text refers to the states shown in the
ABB Drives communication profile
.
Bit
Name
Value
STATE/Description
0
RDY_ON
1
READY TO SWITCH ON.
0
NOT READY TO SWITCH ON.
1
RDY_RUN
1
READY TO OPERATE.
0
OFF1 ACTIVE.
2
RDY_REF
1
OPERATION ENABLED.
0
OPERATION INHIBITED.
3
TRIPPED
1
FAULT.
0
No fault.
4
OFF_2_STA
1
OFF2 inactive.
0
OFF2 ACTIVE.
5
OFF_3_STA
1
OFF3 inactive.
0
OFF3 ACTIVE.
6
SWC_ON_INHIB
1
SWITCH-ON INHIBITED.
0
7
ALARM
1
Warning/Alarm.
0
No Warning/Alarm.
8
AT_SETPOINT
1
OPERATING.
Actual value equals reference value (= is within tolerance limits
i.e in speed control the speed error is less than or equal to 10% of the nominal
motor speed).
0
Actual value differs from reference value (= is outside tolerance limits).
9
REMOTE
1
Drive control location: REMOTE (EXT1 or EXT2).
0
Drive control location: LOCAL.
10
1
Bit is read from the address defined with parameter
MSW B10 PTR.
By default no address has been selected.
0
Actual frequency or speed value is within supervision limit.
11
EXT CTRL LOC
1
External Control Location EXT2 selected.
0
External Control Location EXT1 selected.
12
EXT RUN ENABLE
1
External Run Enable signal received.
0
No External Run Enable received.
13
Bit is read from the address defined with parameter
MSW B13 PTR.
By default no address has been selected.
14
Bit is read from the address defined with parameter
MSW B14 PTR.
By default no address has been selected.
15
1
Communication error detected by fieldbus adapter module (on fibre optic
channel CH0).
0
Fieldbus adapter (CH0) communication OK.
Содержание ACS 800 Series
Страница 1: ...ACS800 Firmware Manual Crane Control Program N697 ...
Страница 4: ......
Страница 26: ...Start up and control through the I O interface 26 ...
Страница 36: ...Quick start up guide 36 ...
Страница 52: ...Control panel 52 ...
Страница 105: ...Program features 105 Figure Control diagram for Shaft synchronisation executed in 20 ms ...
Страница 126: ...Program features 126 The figures below show speed limits according to different load conditions ...
Страница 128: ...Program features 128 ...
Страница 150: ...Application macros control location EXT1 EXT2 150 ...
Страница 228: ...Actual signals and parameters 228 ...
Страница 299: ...Adaptive Programming examples for crane control 299 ...
Страница 305: ...Adaptive Programming examples for crane control 305 ...
Страница 312: ...Adaptive Programming examples for crane control 312 The following figures show the previous example enlarged ...
Страница 314: ...Adaptive Programming examples for crane control 314 The following figures show the previous example enlarged ...
Страница 318: ...Analogue Extension Module 318 ...
Страница 332: ...Additional data actual signals and parameters 332 ...
Страница 333: ...DriveWindow 333 DriveWindow DriveWindow connected to the ACS800 RMIO RDCO board and channel CH3 ...
Страница 334: ...DriveWindow 334 ...
Страница 335: ...Control block diagrams 335 Control block diagrams ...
Страница 336: ...Control block diagrams 336 ...
Страница 337: ...Control block diagrams 337 ...
Страница 338: ...Control block diagrams 338 ...
Страница 340: ...www abb com drives www abb com drivespartners Contact us 3AFE68775230 Rev E EN 2012 09 25 ...