Actual signals and parameters
219
96.06
EXT AO2 PTR
Defines the source or constant for value.
1000 =
1 mA
-255.255.31 …
+255.255.31 / C.-
32768 … C.32767
Parameter index or a constant value. See parameter
for information on
the difference.
-
96.07
INVERT EXT AO2
Activates the inversion of analogue output AO2 of the analogue I/O extension
module. The analogue signal is at its minimum level when the drive signal
indicated is at its maximum and vice versa.
NO
Inactive
0
YES
Active
65535
96.08
MINIMUM EXT AO2
Defines the minimum value for analogue output AO2 of the analogue I/O
extension module. See parameter
0 mA
0 mA
1
4 mA
4 mA
2
10 mA
10 mA
3
12 mA
12 mA
4
96.09
FILTER EXT AO2
Defines the filtering time constant for analogue output AO2 of the analogue I/O
extension module. See parameter
0.00 … 10.00 s
Filtering time constant
0 … 1000
96.10
SCALE EXT AO2
Defines the scaling factor for analogue output AO2 of the analogue I/O
extension module. See parameter
10 … 1000%
Scaling factor
100 …
10000
97 MOTOR MODEL
97.12
EM STOP DIO
Enables emergency stop commands through the RDIO module located on the
RMIO board (RDIO-SLOT1 or RDIO-SLOT2) or in the external I/O Module
Adapter AIMA (RDIO-DDCS).
- RDIO digital input 1 (DI1) = OFF2 STOP
- RDIO digital input 2 (DI2) = OFF3 STOP
The OFF3 deceleration time is defined by parameter
TIME.
NO
Emergency stop through the RDIO module is not in use.
1
RDIO-SLOT1
OFF2 STOP (through DI1) and/or OFF3 STOP (through DI2) is taken from the
RDIO module located in option SLOT 1.
2
RDIO-SLOT2
OFF2 STOP (through DI1) and/or OFF3 STOP (through DI2) is taken from the
RDIO module located in option SLOT 2.
3
RDIO-DDCS
OFF2 STOP (through DI1) and/or OFF3 STOP (through DI2) is taken from the
RDIO module located on the AIMA I/O Module Adapter (RDIO-DDCS).
Note:
If RDIO-DDCS is selected, the module node number must be set to 7.
4
97.16
SPD CORR PTR
Speed correction pointer. Default: +.000.000.00. Defines external speed
correction by writing it to signal SPEED CORR BUFF (
). Speed correction
pointer is to be used only when Synchro control is not used.
-255.255.31 …
+255.255.31 / C.-
32768 … C.32767
Parameter index or a constant value.
97.17
APL LIM WRN MASK Application limit warning mask. Default 0000 0001 1111 1000 b (binary mode).
This parameter can block application messages not required for the control
panel display.
Index
Name/Selection
Description
FbEq
Содержание ACS 800 Series
Страница 1: ...ACS800 Firmware Manual Crane Control Program N697 ...
Страница 4: ......
Страница 26: ...Start up and control through the I O interface 26 ...
Страница 36: ...Quick start up guide 36 ...
Страница 52: ...Control panel 52 ...
Страница 105: ...Program features 105 Figure Control diagram for Shaft synchronisation executed in 20 ms ...
Страница 126: ...Program features 126 The figures below show speed limits according to different load conditions ...
Страница 128: ...Program features 128 ...
Страница 150: ...Application macros control location EXT1 EXT2 150 ...
Страница 228: ...Actual signals and parameters 228 ...
Страница 299: ...Adaptive Programming examples for crane control 299 ...
Страница 305: ...Adaptive Programming examples for crane control 305 ...
Страница 312: ...Adaptive Programming examples for crane control 312 The following figures show the previous example enlarged ...
Страница 314: ...Adaptive Programming examples for crane control 314 The following figures show the previous example enlarged ...
Страница 318: ...Analogue Extension Module 318 ...
Страница 332: ...Additional data actual signals and parameters 332 ...
Страница 333: ...DriveWindow 333 DriveWindow DriveWindow connected to the ACS800 RMIO RDCO board and channel CH3 ...
Страница 334: ...DriveWindow 334 ...
Страница 335: ...Control block diagrams 335 Control block diagrams ...
Страница 336: ...Control block diagrams 336 ...
Страница 337: ...Control block diagrams 337 ...
Страница 338: ...Control block diagrams 338 ...
Страница 340: ...www abb com drives www abb com drivespartners Contact us 3AFE68775230 Rev E EN 2012 09 25 ...