Actual signals and parameters
205
60.11
SLAVE MODE
Defines the Follower control mode. To be defined only in the Master drive. This
defines the Master signal 3 (see parameter
) to be used according to the
slave mode.
SPEED
The Follower drives are configured for speed control. For example,: Follower
drives are in Shaft synchro mode.
1
TORQUE
The Follower drives are configured for torque control. For example, Follower
drives are in load sharing mode.
2
70 DDCS CONTROL
Settings for the fibre optic channels 0, 1 and 3.
70.01
CHANNEL 0 ADDR
Defines the node address for channel 0. No two nodes on-line may have the
same address. The setting needs to be changed when a master station is
connected to channel 0 and it does not automatically change the address of
the slave. Examples of such masters are an ABB Advant Controller or another
drive.
1 … 125
Address.
1 … 125
70.02
CHANNEL 3 ADDR
Node address for channel 3. No two nodes on-line may have the same
address. Typically the setting needs to be changed when the drive is
connected in a ring which consists of several drives and a PC with the
DriveWindow program running.
1 … 254
Address.
1 … 254
70.03
CH1 BAUD RATE
The communication speed of channel 1. Typically the setting needs to be
changed only if the pulse encoder interface module is connected to channel 1
instead of channel 2. Then the speed must be changed to 4 Mbit/s. See also
parameter
8 Mbit/s
8 megabits per second
0
4 Mbit/s
4 megabits per second
1
2 Mbit/s
2 megabits per second
2
1 Mbit/s
1 megabits per second
3
70.04
CH0 DDCS HW
CONN
Selects the topology of the channel 0 link.
RING
Devices are connected in ring topology.
0
STAR
Devices are connected in a star topology.
1
70.05
CH2 HW
CONNECTION
Selects the topology of the channel 2 link.
Note:
Only the RING topology is supported.
RING
Devices are connected in ring topology.
0
STAR
Devices are connected in a star topology. Not supported.
1
74 SPEED MONITOR
Settings for Speed monitoring. See section
on page
85.
74.01
MOT OVERSPEED
LEV
Defines the motor overspeed level in percentage of maximum speed (Par.
). The value is applicable in both forward and reverse direction. The drive
trips indicating MOTOROVER SPD when the motor speed exceeds this level.
0 … 200 %
Percent.
0 … 2000
Index
Name/Selection
Description
FbEq
Содержание ACS 800 Series
Страница 1: ...ACS800 Firmware Manual Crane Control Program N697 ...
Страница 4: ......
Страница 26: ...Start up and control through the I O interface 26 ...
Страница 36: ...Quick start up guide 36 ...
Страница 52: ...Control panel 52 ...
Страница 105: ...Program features 105 Figure Control diagram for Shaft synchronisation executed in 20 ms ...
Страница 126: ...Program features 126 The figures below show speed limits according to different load conditions ...
Страница 128: ...Program features 128 ...
Страница 150: ...Application macros control location EXT1 EXT2 150 ...
Страница 228: ...Actual signals and parameters 228 ...
Страница 299: ...Adaptive Programming examples for crane control 299 ...
Страница 305: ...Adaptive Programming examples for crane control 305 ...
Страница 312: ...Adaptive Programming examples for crane control 312 The following figures show the previous example enlarged ...
Страница 314: ...Adaptive Programming examples for crane control 314 The following figures show the previous example enlarged ...
Страница 318: ...Analogue Extension Module 318 ...
Страница 332: ...Additional data actual signals and parameters 332 ...
Страница 333: ...DriveWindow 333 DriveWindow DriveWindow connected to the ACS800 RMIO RDCO board and channel CH3 ...
Страница 334: ...DriveWindow 334 ...
Страница 335: ...Control block diagrams 335 Control block diagrams ...
Страница 336: ...Control block diagrams 336 ...
Страница 337: ...Control block diagrams 337 ...
Страница 338: ...Control block diagrams 338 ...
Страница 340: ...www abb com drives www abb com drivespartners Contact us 3AFE68775230 Rev E EN 2012 09 25 ...