09 CDP CONTROL PANEL
3BHS212794 E01 REV M
ACS6000
USER MANUAL
206/278
6.
To confirm the selection and to return to the actual signals display,
press the ENTER key.
7.
To cancel the selection and keep the original selection, press any of
the mode selection keys. The selected keypad mode is entered.
9.2.2.6
Displaying a fault and resetting the fault memory
1.
To open the actual signals display, press the ACT key.
2.
To change to the fault memory display, press a fast navigation key.
1 L ->
600.0 rpm