Safety Instructions
viii
ACx = ACS/ACC/ACP
ACS/ACC/ACP 604/607 AC Drives
Without Filter
Below is a diagram of
V
PK
and
dv/dt as a function of cable length when
no dv/dt filter is used.
With dv/dt Filter
Below is a diagram of
V
PK
and
dv/dt as a function of cable length with
dv/dt filter at the output of the ACx 600.
Power Factor
Correction Capacitors
Power factor correction capacitors and surge absorbers must not be
connected between the drive and the motor. These devices are not
designed to be used with AC drives, and will degrade motor control
accuracy. They can cause permanent damage to the ACx 600 or
themselves due to the rapid changes in the ACx 600 output voltage.
0
0,5
1
1,5
2
2,5
3
3,5
4
4,5
5
0
50
100
150
200
250
300
dv/dt / (kV/
µ
s)
V
PK
/ V
N
Cable length
0
1000
500
(m)
(feet)
0
0,5
1
1,5
2
2,5
3
3,5
4
4,5
5
0
50
100
150
200
250
300
dv/dt / (kV/
µ
s)
V
PK
/ V
N
0
1000
500
(feet)
(m)
Cable length
Содержание ACS 600 Series
Страница 2: ......
Страница 4: ......
Страница 16: ...xiv ACx ACS ACC ACP ACS ACC ACP 604 607 Drives ...
Страница 20: ...Chapter 1 Introduction 1 4 ACx ACS ACC ACP ACS ACC ACP 604 607 Drives ...
Страница 38: ...Chapter 5 Maintenance 5 2 ACx ACS ACC ACP ACS ACC ACP 604 607 Drives ...
Страница 72: ...Appendix B ACx 607 Dimensional Drawings B 2 ACx ACX ACC ACP ACS ACC ACP 604 607 Drives ...
Страница 81: ......