ACS 600 MultiDrive – Technical Data
A-22
ACS 600 MultiDrive
Efficiency and
Cooling Method
Efficiency:
Approximately 98 % at nominal power level and frequency.
For units equipped with IGBT supply unit approximately 96 %.
Cooling Method:
Internal fan, flow direction from the bottom to the top
Ambient Conditions
Environmental limits of the ACS 600 MultiDrive frequency converters
are given below.
1)
At sites over 1000 m above sea level, the maximum output current is derated as
follows.
I
max
=
I
N40C
· (100 % - 1 % · (
h
- 1000 m)/(100 m) + 1.5 % · (40 °C -
T
amb
))
where
h
altitude above sea level
I
N40C
ACS 600 nominal current at 40 °C
T
amb
maximum ambient temperature.
Note:
I
max <
I
N40C
and
T
amb
< 40 °C. At 2000...4000 m optional “varistors” are needed.
2)
If the ambient temperature is higher than +40 °C (+35 °C), the output capacity of the
ACx 600 decreases. The output current is calculated by multiplying the current given in
the rating table by the derating factor.
Condition
Operation
installed for stationary use
Storage
in the protective package
Transportation
in the protective package
Installation Site
Altitude
Nominal output power at 0 to
1000 m above sea level
1)
-
-
Air Temperature
0 to +40 °C
2)
(IP 21/22/42)
0 to +35 °C
2)
(IP 54R)
-40 to +70 °C -40
to
+70
°C
Relative Humidity
5 to 95 %
Max. 95 %
Max. 95 %
No condensation allowed. Maximum allowed relative humidity is 60 % in the presence of
corrosive gases.
Contamination
Levels
(IEC 721-3-3)
No conductive dust allowed.
Boards without coating:
Chemical gases: Class 3C1
Solid particles: Class 3S2
Boards with coating:
Chemical gases: Class 3C2
Solid particles: Class 3S2
Boards without coating:
Chemical gases: Class 1C2
Solid particles: Class 1S3
Boards with coating:
Chemical gases: Class 1C2
Solid particles: Class 1S3
Boards without coating:
Chemical gases: Class 2C2
Solid particles: Class 2S2
Boards with coating:
Chemical gases: Class 2C2
Solid particles: Class 2S2
Atmospheric
Pressure
70 to 106 kPa
70 to 106 kPa
60 to 106 kPa
Vibration
(IEC 68-2-6)
Max. 0.3 mm (2 to 9 Hz),
max. 1 m/s
2
(9 to 200 Hz)
sinusoidal
Max. 1.5 mm (2 to 9 Hz),
max. 5 m/s
2
(9 to 200 Hz)
sinusoidal
Max. 3.5 mm (2 to 9 Hz),
max. 15 m/s
2
(9 to 200 Hz)
sinusoidal
Shock
(IEC 68-2-29)
Not allowed
Max. 100 m/s
2
, 11 ms
Max. 100 m/s
2
, 11 ms
Free Fall
Not allowed
250 mm (weight under 100 kg)
100 mm (weight over 100 kg)
250 mm (weight under 100 kg)
100 mm (weight over 100 kg)
Содержание ACS 600 MultiDrive
Страница 4: ......
Страница 7: ...ACS 600 MultiDrive v Applicable Standards B 2 Materials B 2 Other Technical Data B 2...
Страница 8: ...vi ACS 600 MultiDrive...
Страница 24: ...Safety Instructions 16 ACS 600 MultiDrive...
Страница 69: ......