Electrical installation 73
Connecting the power cables
Connection diagram
1.
For alternatives, see section
Selecting the supply disconnecting device (disconnecting means)
on page
2.
If shielded cable is used (not required but recommended) and the conductivity of the shield is < 50% of
the conductivity of the phase conductor, use a separate PE cable (2) or a cable with a grounding
conductor (3).
3.
as 2)
4.
360 degrees grounding is recommended at the cabinet entry if shielded cable is used. Ground the other
end of the input cable shield or PE conductor at the distribution board.
5.
360 degrees grounding at the cabinet entry is recommended, see page
6.
Use a separate grounding cable if the conductivity of the cable shield is < 50% of the conductivity of the
phase conductor and there is no symmetrically constructed grounding conductor in the cable (see page
).
7.
du/dt filter or sine filter (optional, see page
).
Note:
If there is a symmetrically constructed grounding conductor in the motor cable in addition to the conductive
shield, connect the grounding conductor to the grounding terminal at the drive and motor ends.
Do not use an asymmetrically constructed motor cable. Connecting its fourth conductor at the motor end
increases bearing currents and causes extra wear.
INPUT
OUTPUT
U1 V1 W1
2)
U2 V2 W2
UDC+
R+
UDC
-
R
-
L1
L2
L3
(PE)
(PE)
PE
3)
ACQ810-04
PE
1)
4)
5)
U1
V1
W1
3
~
Motor
6)
7)
Содержание ACQ810
Страница 1: ...ABB industrial drives Hardware manual ACQ810 drive modules 200 to 400 kW 250 to 600 hp...
Страница 4: ......
Страница 16: ...16 Safety instructions...
Страница 30: ...30 Operation principle and hardware description...
Страница 69: ...Planning the electrical installation 69 Example circuit diagram See page 129...
Страница 70: ...70 Planning the electrical installation...
Страница 88: ...88 Electrical installation...
Страница 94: ...94 Start up...
Страница 96: ...96 Fault tracing...
Страница 122: ...122 Dimension drawings Frame without pedestal mm 64801082_3 6 E Center of gravity...
Страница 123: ...Dimension drawings 123 Frame with busbars on the left side mm 64801082_5 6 E...
Страница 124: ...124 Dimension drawings Drive control unit JCU Can be mounted on a DIN rail EN 50022 35 mm x 7 5 mm...
Страница 125: ...Dimension drawings 125 Package...
Страница 127: ...Dimension drawings 127 Frame with busbars on the left side inches 68440513_5 6 A 64801082 asm E...
Страница 128: ...128 Dimension drawings...
Страница 132: ...132 du dt filters and sine filters Sine filters Contact your local ABB representative...