![ABB ACQ810 Скачать руководство пользователя страница 64](http://html1.mh-extra.com/html/abb/acq810/acq810_hardware-manual_3423066064.webp)
64 Planning the electrical installation
Implementing the Safe torque off function
The drive supports the Safe torque off function according to standards
EN 61800-5-2:2007; EN 954-1:1997; IEC/EN 60204-1:1997; EN 61508:2002 and
EN 1037:1996.
The Safe torque off function disables the control voltage of the power semiconductors of
the drive output stage, thus preventing the inverter from generating the voltage required to
rotate the motor (see diagram below). By using this function, short-time operations (like
cleaning) and/or maintenance work on non-electrical parts of the machinery can be
performed without switching off the power supply to the drive.
WARNING!
The Safe torque off function does not disconnect the voltage of the
main and auxiliary circuits from the drive. Therefore maintenance work on
electrical parts of the drive or the motor can only be carried out after isolating the
drive system from the main supply.
Note:
It is not recommended to stop the drive by using the Safe torque off function. If a
running drive is stopped by using the Safe torque off function, the drive will stop by
coasting. If this causes danger or is not acceptable, the drive and machinery must be
stopped using the appropriate stopping mode before using the Safe torque off function.
+24 V
XSTO:1
XSTO:2
XSTO:3
XSTO:4
U2/V2/W2
Control
circuit
UDC+
UDC-
ACQ810-04
Output stage
(1 phase shown)
Safe torque off
connection on JCU
Activation switch
Notes:
• The contacts of the activation
switch must open/close within
200 ms of each other.
• The maximum cable length
between the drive and the
activation switch is 25 m (82 ft)
Содержание ACQ810
Страница 1: ...ABB industrial drives Hardware manual ACQ810 drive modules 200 to 400 kW 250 to 600 hp...
Страница 4: ......
Страница 16: ...16 Safety instructions...
Страница 30: ...30 Operation principle and hardware description...
Страница 69: ...Planning the electrical installation 69 Example circuit diagram See page 129...
Страница 70: ...70 Planning the electrical installation...
Страница 88: ...88 Electrical installation...
Страница 94: ...94 Start up...
Страница 96: ...96 Fault tracing...
Страница 122: ...122 Dimension drawings Frame without pedestal mm 64801082_3 6 E Center of gravity...
Страница 123: ...Dimension drawings 123 Frame with busbars on the left side mm 64801082_5 6 E...
Страница 124: ...124 Dimension drawings Drive control unit JCU Can be mounted on a DIN rail EN 50022 35 mm x 7 5 mm...
Страница 125: ...Dimension drawings 125 Package...
Страница 127: ...Dimension drawings 127 Frame with busbars on the left side inches 68440513_5 6 A 64801082 asm E...
Страница 128: ...128 Dimension drawings...
Страница 132: ...132 du dt filters and sine filters Sine filters Contact your local ABB representative...