Fiber optic cables
Printed circuit boards
Safe start-up and operation
General safety
These warnings are intended for all who plan the operation of the drive or operate the
drive.
WARNING!
Ignoring the following instructions can cause equipment malfunction
and damage to the fiber optic cables:
•
Handle the fiber optic cables with care. When unplugging optic cables, always grab
the connector, not the cable itself. Do not touch the ends of the fibers with bare
hands as the fiber is extremely sensitive to dirt. The minimum allowed bend radius is
35 mm (1.4 in.).
WARNING!
Ignoring the following instructions can cause damage to the printed
circuit boards:
•
The printed circuit boards contain components sensitive to electrostatic discharge.
Wear a grounding wrist band when handling the boards. Do not touch the boards
unnecessarily.
WARNING!
Ignoring the following instructions can cause physical injury or
death, or damage to the equipment:
•
Before adjusting the drive and putting it into service, make sure that the motor and all
driven equipment are suitable for operation throughout the speed range provided by
the drive. The drive can be adjusted to operate the motor at speeds above and below
the speed provided by connecting the motor directly to the power line.
•
Do not activate any automatic fault reset functions of the drive control program if
dangerous situations can occur. When activated, these functions will reset the drive
and resume operation after a fault.
•
Do not control the motor with an AC contactor or disconnecting device
(disconnecting means); instead, use the control panel keys
and
, or
commands via the I/O board of the drive. The maximum allowed number of charging
cycles of the DC capacitors ie, power-ups by applying power, is five in ten minutes.
Note:
•
If an external source for start command is selected and it is ON, the drive will start
immediately after an input voltage break or fault reset unless the drive is configured
for 3-wire (a pulse) start/stop.
•
When the control location is not set to local, the stop key on the control panel will not
stop the drive.
Содержание ACQ810
Страница 1: ...ABB industrial drives Hardware manual ACQ810 drive modules 200 to 400 kW 250 to 600 hp...
Страница 4: ......
Страница 16: ...16 Safety instructions...
Страница 30: ...30 Operation principle and hardware description...
Страница 69: ...Planning the electrical installation 69 Example circuit diagram See page 129...
Страница 70: ...70 Planning the electrical installation...
Страница 88: ...88 Electrical installation...
Страница 94: ...94 Start up...
Страница 96: ...96 Fault tracing...
Страница 122: ...122 Dimension drawings Frame without pedestal mm 64801082_3 6 E Center of gravity...
Страница 123: ...Dimension drawings 123 Frame with busbars on the left side mm 64801082_5 6 E...
Страница 124: ...124 Dimension drawings Drive control unit JCU Can be mounted on a DIN rail EN 50022 35 mm x 7 5 mm...
Страница 125: ...Dimension drawings 125 Package...
Страница 127: ...Dimension drawings 127 Frame with busbars on the left side inches 68440513_5 6 A 64801082 asm E...
Страница 128: ...128 Dimension drawings...
Страница 132: ...132 du dt filters and sine filters Sine filters Contact your local ABB representative...