92 Application macros
Hand/Auto control macro
Description and typical application
Start and stop commands and references (setpoints) can be given from one of two
external control locations, EXT1 (Hand) or EXT2 (Auto). The start/stop commands
received through EXT1 (Hand) are connected to digital input DI1, while the reference
is connected to analog input AI1. The start/stop commands from EXT2 (Auto) are
connected to DI2 while the reference is connected to AI2. The selection between
Hand/Auto is dependent on the status of DI5. The drive is speed-controlled. The
speed reference and start/stop commands can also be given from the control panel.
Default settings
Below is a listing of default parameter values that differ from those listed in chapter
(page
Parameter
Hand/Auto macro
default
No.
Name
C.FALSE