242 Parameters
Reg bypass
PID controller bypass mode.
The signal selected by parameters
is used as
the reference. The automatic starting and stopping of direct-
on-line pumps is related to this actual value instead of the
output of the PID controller.
This setting can be used in applications with a low number of
sensors and low accuracy requirements.
Example:
The capacity of the pumping station (outlet flow)
follows the measured inlet flow.
2
In the diagram below, the slopes of the lines describe the
relation between the control signal (selected by parameters
) and the speed of the controlled pump in a
three-motor system. At full control signal level, all pumps are
operating at maximum speed.
No.
Name/Value
Description
FbEq
M
3~
M
3~
M
3~
3
3
3
3
3
3
Measured inlet flow = Reference for the pumping station
P3
P2
P1
P1
P2
P3
Inlet
pipe
Outlet
pipe 1
Outlet
pipe 2
Sewage
tank
Contac-
tors
3-phase
supply
Drive
Outlet
pipe 3
Control signal (%)
No aux. mo-
tors ON
Stop speed 2
Max. speed.
Start speed 2
Start speed 1
Min. speed.
Speed (rpm)
33%
66%
100%
Stop speed 1
1 aux. motor
ON
2 aux. mo-
tors ON
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...