236 Parameters
58.11
Reference scale
Defines the factor which the DCU 16-bit communication
profile uses when scaling fieldbus references to drive
references and drive actual values to fieldbus actual signals.
The references are multiplied by this scaling factor. See
section
on page
1…65535
Scaling factor.
1 = 1
58.15
Comm diagnostics
16-bit packed boolean data word for the communication
diagnostics flag bits. Read only.
0x0000…0xFFFF
Data word (hex).
1 = 1
58.16
Received packets
Shows
the number of message packets received by the
drive, including only such packets that are addressed to the
drive.
Note:
The user can reset the counter (by setting the
value to 0).
0…65535
No. of message packets.
1 = 1
58.17
Transm packets
Shows the number of message packets sent by the drive.
Note:
The user can reset the counter (by setting the value to
0).
0…65535
No. of message packets.
1 = 1
58.18
All packets
Shows the total number of message packets received by the
drive, including all packets addressed to any valid node on
the fieldbus link.
Note:
The user can reset the counter (by
setting the value to 0).
0…65535
No. of message packets.
1 = 1
58.19
UART errors
Shows the number of messages with communication errors
other than CRC errors which the drive has received (e.g.
UART buffer overflow errors). Read only.
0..65535
No. of messages with errors (excluding messages with CRC
errors).
1 = 1
58.20
CRC errors
Shows the number of messages with Cyclic Redundancy
Check (CRC) errors which the drive has received. Read
only.
Note:
High electromagnetic noise levels may generate
errors.
No.
Name/Value
Description
FbEq
Bit
Information
0
Reserved.
1
Last received packet was not for this node.
2
Reserved.
3
At least one packet has been successfully received after the power up.
4
Reserved.
5
Communication time-out has occured.
6…7
Reserved.
8
Last write was not successful because of a parameter value limit violation.
9
Last read was not successful because only one register was used to read a 32-bit value.
10
Last write was not successful because the parameter was read only.
11
Last parameter access was not successful because the parameter or group did not exist.
12…14 Reserved.
15
Last write was not successful because only one register was used to read a 32-bit value.
16…31 Reserved.
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...