Parameters 193
lbsi
lbsi
61
m
m
72
inch
inch
73
28.07
Act FBA scaling
Defines a divisor for process actual value for fieldbus. This
parameter can be used to improve calculation accuracy at
low and high values.
Not used
No scaling applied.
0
Src/10
The actual value is divided by 10 for fieldbus.
1
Src/100
The actual value is divided by 100 for fieldbus.
2
Src/1000
The actual value is divided by 1000 for fieldbus.
3
29
29 Setpoint sel
Process setpoint (reference) settings.
29.01
Setpoint 1 / 2 sel
Selects the process setpoint (1 or 2). Alternatively, selects a
source whose status determines which process setpoint is
used (0 = Setpoint 1; 1 = Setpoint 2).
Setpoint 1
Setpoint 1 selected.
0
Setpoint 2
Setpoint 2 selected.
1
DI1
Status of digital input DI1 (as indicated by
, bit
0) determines which process setpoint is selected.
1073742337
DI2
Status of digital input DI2 (as indicated by
, bit
1) determines which process setpoint is selected.
1073807873
DI3
Status of digital input DI3 (as indicated by
, bit
2) determines which process setpoint is selected.
1073873409
DI4
Status of digital input DI4 (as indicated by
, bit
3) determines which process setpoint is selected.
1073938945
DI5
Status of digital input DI5 (as indicated by
, bit
4) determines which process setpoint is selected.
1074004481
Const
Bit pointer setting (see
on page
-
Pointer
29.02
Setpoint 1 src
Selects the source of process setpoint 1.
Zero
No source selected.
0
AI1 scaled
(see page
).
1073742341
AI2 scaled
(see page
).
1073742343
AI3 scaled
(see page
).
1073742345
AI4 scaled
(see page
).
1073742347
AI5 scaled
(see page
).
1073742349
FBA setpoint
(see page
).
1073742376
Shared sig2
(see page
).
1073742380
Int set 1
(see below).
1073749252
Pointer
Value pointer setting (see
on page
-
29.03
Setpoint 2 src
Selects the source of process setpoint 2.
Zero
No source selected.
0
AI1 scaled
).
1073742341
AI2 scaled
).
1073742343
No.
Name/Value
Description
FbEq
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...