![ABB ACQ810 Скачать руководство пользователя страница 126](http://html.mh-extra.com/html/abb/acq810/acq810_firmware-manual_2549126.webp)
126 Parameters
05.35
kWh December
Energy consumed during last December.
1 = 1 kWh
05.36
First in order
The first pump in the current Autochange sequence.
1 = 1
05.37
Time autochg
Time elapsed since last Autochange.
1 = 1 ms
05.39
Next start node
(Only valid when the drive is master.) Node number of the
next drive to be started.
1 = 1
06
06 Drive status
Drive status words.
06.01
Status word1
Status word 1 of the drive.
-
No.
Name/Value
Description
FbEq
Bit
Name
Information
0
Ready
1 = Drive is ready to receive start command.
0 = Drive is not ready.
1
Enabled
1 = External run enable signal is received.
0 = No external run enable signal is received.
2
Started
1 = Drive has received start command.
0 = Drive has not received start command.
3
Running
1 = Drive is modulating.
0 = Drive is not modulating.
4
Em off
(off2)
1 = Emergency OFF2 is active.
0 = Emergency OFF2 is inactive.
5
Em stop
(off3)
1 = Emergency OFF3 (ramp stop) is active.
0 = Emergency OFF3 is inactive.
6
Ack startinh 1 = Start inhibit is active.
0 = Start inhibit is inactive.
7
Alarm
1 = Alarm is active. See chapter
.
0 = No alarm is active.
8
Ext2 act
1 = External control EXT2 is active.
0 = External control EXT1 is active.
9
Local fb
1 = Fieldbus local control is active.
0 = Fieldbus local control is inactive.
10
Fault
1 = Fault is active. See chapter
.
0 = No fault is active.
11
Local panel 1 = Local control is active, ie. drive is controlled from PC tool or control
panel.
0 = Local control is inactive.
12
Fault(-1)
1 = No fault is active.
0 = Fault is active. See chapter
.
13…15 Reserved
Содержание ACQ810
Страница 1: ...ABB industrial drives Firmware manual Standard pump control program for ACQ810 drives ...
Страница 4: ......
Страница 14: ...14 About the manual ...
Страница 56: ...56 Control locations ...
Страница 97: ...Application macros 97 ...
Страница 98: ...98 Application macros ...
Страница 100: ...100 Application macros ...
Страница 101: ...Application macros 101 ...
Страница 106: ...106 Application macros 75 01 Operation mode Multipump 76 01 Enable MF comm Yes ...
Страница 356: ...356 Control through the embedded fieldbus interface ...
Страница 366: ...366 Control through a fieldbus adapter ...
Страница 374: ...374 Control block diagrams ...