86
ACQ800-37 Hardware Manual
Installation checklist and start-up
Start-up procedure
Action
Additional information
WARNING!
Ensure that the disconnector of the supply transformer is
locked to open position, i.e. no voltage is, or cannot be connected to
drive inadvertently. Check also by measuring that there is no voltage
connected.
Basic checks with no voltage connected
If the unit is equipped with an air circuit breaker, check the current trip
limits of the breaker (preset at the factory).
General rule
Ensure the selectivity condition is fulfilled i.e. the breaker trips at a lower
current than the protection device of the supplying network, and that the
limit is high enough not to cause unnecessary trips during the
intermediate DC circuit load peak at start.
Long-term current limit
As a rule of thumb, this should be set to the rated AC current of the drive.
Peak current limit
As a rule of thumb, this should be set to a value 3-4 times the rated AC
current of the drive.
Optional device. See the delivery-
specific circuit diagrams.
Check the settings of the relays and breakers/switches of the auxiliary
circuits.
Optional devices. See delivery
specific circuit diagrams.
Disconnect any unfinished or unchecked 230/115 V AC cables that lead
from the terminal blocks to the outside of the equipment.
Connecting voltage to input terminals and auxiliary circuit
WARNING!
When voltage is connected to the input terminals, voltage
may also be connected to the auxiliary circuits of the drive.
Make sure that it is safe to apply voltage. Ensure that:
• nobody is working on the unit or circuits that are wired from outside into
the cabinets
• cabinet doors are closed
• covers of motor terminal boxes are in place.
Close the main breaker of the supply transformer.
Close the auxiliary circuit On/Off switch (Q100) if present.
Starting the supply unit
Close the main switch/disconnector (Q1).
Units with emergency stop: Turn the Start switch on the cabinet door
from 0 into START position for 2 seconds, then release the switch and
leave it in position 1.
Checks with the supply unit running
Check the settings of the earth fault (ground fault) monitoring device (if
present).
See chapter
.
Содержание ACQ800 Series
Страница 1: ...Hardware Manual ACQ800 37 Drives 55 to 450 kW 75 to 550 hp ACQ800 ...
Страница 4: ......
Страница 12: ...12 ACQ800 37 Hardware Manual Safety instructions ...
Страница 24: ...24 ACQ800 37 Hardware Manual About this manual ...
Страница 52: ...52 ACQ800 37 Hardware Manual Mechanical installation ...
Страница 78: ...78 ACQ800 37 Hardware Manual Electrical installation ...
Страница 84: ...84 ACQ800 37 Hardware Manual Motor control and I O board RMIO ...
Страница 92: ...92 ACQ800 37 Hardware Manual Installation checklist and start up ...
Страница 106: ...106 ACQ800 37 Hardware Manual Maintenance 3 4 5 6 8 7b 7a ...
Страница 107: ...ACQ800 37 Hardware Manual 107 Maintenance 9 10 11 View from back ...
Страница 123: ...ACQ800 37 Hardware Manual 123 Technical data Declaration of Conformity ...
Страница 124: ...124 ACQ800 37 Hardware Manual Technical data ...
Страница 128: ...128 ACQ800 37 Hardware Manual Dimensions Frame R6 ...
Страница 129: ...ACQ800 37 Hardware Manual 129 Dimensions Frame R6 continued ...
Страница 130: ...130 ACQ800 37 Hardware Manual Dimensions Frame R7i ...
Страница 131: ...ACQ800 37 Hardware Manual 131 Dimensions Frame R7i continued ...
Страница 132: ...132 ACQ800 37 Hardware Manual Dimensions Frame R7i continued ...
Страница 133: ...ACQ800 37 Hardware Manual 133 Dimensions Frame R7i continued ...
Страница 134: ...134 ACQ800 37 Hardware Manual Dimensions Frame R8i ...
Страница 135: ...ACQ800 37 Hardware Manual 135 Dimensions Frame R8i continued ...
Страница 136: ...136 ACQ800 37 Hardware Manual Dimensions Frame R8i continued ...
Страница 137: ...ACQ800 37 Hardware Manual 137 Dimensions Frame R8i continued ...
Страница 138: ...138 ACQ800 37 Hardware Manual Dimensions ...