Startup, control with I/O and ID run 27
ID run procedure
With the ID run assistant
Pre-check
WARNING!
The motor will run at up to approximately 50…80% of the
nominal speed during the ID run. The motor will rotate in the forward
direction.
Make sure that it is safe to run the motor before performing the
ID run.
Do not do ID run on a rotating motor. Make sure that the motor is
stopped before starting the ID run.
Decouple the motor from the driven equipment
Check that the values of the motor data parameters are equivalent to those on the
motor nameplate.
Check that the STO circuit is closed.
The assistant will ask if you want to use temporary motor limits. They must meet
the following conditions:
Minimum speed < 0 rpm
Maximum speed = motor rated speed (Normal ID run procedure needs the motor
to be run at 100% speed.)
Maximum current > 0.5 x motor nominal current
Maximum torque > 50%
Make sure that the control panel is in local control (text Local shown at the top
left). Press key
to switch between local and remote control.
ID run
Go to the
Main
menu by pressing
(
Menu
) in the Home view.
Select
Primary settings
and press
(
Select
) (or
).
Select
Motor
and press
(
Select
) (or
).
Loc/Rem
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...