Startup, control with I/O and ID run 25
How to control the drive through the I/O interface
The table below describes how to operate the drive through the digital and
analog inputs when:
• the motor startup is performed, and
• the default parameter settings of the ABB standard macro are in use.
Preliminary settings
If you need to change the direction of rotation,
check that limits allow reverse direction: Go to
Menu - Primary settings - Limits
and make sure
that the minimum limit has a negative value and
the maximum limit has a positive value.
Make sure that the control connections are wired
according to the connection diagram given for the
ABB standard macro.
Note:
Most of the macros uses I/O that exist only
when I/O module is installed. If you do not use it,
choose ABB limited macro or change the default
use of the I/O by parameters.
connections for the ABB standard
macro
on page
Make sure that the drive is in remote control. Press
key
to switch between remote and local
control.
In remote control, the control panel
display shows text
Remote
at the
top left.
Starting and controlling the speed of the motor
Start by switching digital input DI1 on.
The arrow starts rotating. It is dotted until the
setpoint is reached.
Regulate the drive output frequency (motor
speed) by adjusting voltage of analog input AI1.
Stopping the motor
Switch digital input DI1 off. The arrow stops
rotating.
Loc/Rem
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...