Diagnostics 57
EN
TR
ZH
Diagnostics
Warning messages
Code
(hex)
Warning/Aux code
(
aux code
visible only on assistant control
panel and drive composer
)
Cause
What to do
64FF
Fault reset
A fault has been reset.
Event. Informative only.
A2B1 Overcurrent
Output current exceeded
internal fault limit.
Check motor load, acceleration
times, earth fault in motor or motor
cables, contactors opening and
closing, start-up data, power factor
correction in capacitors or surge
absorbers in motor cable.
A2B3 Earth leakage
Load unbalance typically due to
earth fault in motor or motor
cable.
Check for no power factor
correction capacitors or surge
absorbers in motor cable, and no
earth fault in motor or motor cables.
A2B4 Short circuit
Short-circuit in motor cable(s) or
motor.
Check motor and motor cable for
cabling errors, no earth fault in
motor or motor cables, no power
factor correction capacitors or surge
absorbers in motor cable.
A2BA IGBT overload
Excessive IGBT junction to case
temperature.
Check motor cable, ambient
conditions, air flow and fan
operation, heatsink fins for dust
pick-up, motor power against drive
power.
A3A1 DC link overvoltage
Intermediate circuit DC voltage
too high.
Check Overvoltage control
parameter, no static or transient
overvoltage in mains voltage, brake
chopper/resistor, and deceleration
time. Use coast-to-stop. Retrofit
drive with chopper and resistor.
A3A2 DC link undervoltage
Intermediate circuit DC voltage
too low (when the drive is
stopped).
Check the supply voltage setting
and fuses.
A3AA DC not charged
The voltage of the intermediate
DC circuit has not rose to
operating level.
Check the supply voltage and
supply voltage setting.
A490
Incorrect temperature sensor
setup
Sensor type mismatch
Check the temperature setting
parameters.
A491
External temperature 1
Measured temperature 1
exceeded warning limit.
, cooling of
the motor, value of
.
A492
External temperature 2
Measured temperature 2
exceeded warning limit.
, cooling of
the motor, value of
.
A4A0 Control board temperature.
Control board temperature is
excessive.
1 – Sensor fault.
Check the sensor and change the
control board.
ACQ80R0-R8 QIG.book Page 57 Friday, February 1, 2019 1:18 PM