50 Parameters List
EN
ES
FI
FR
IT
PL
PT
RU
SV
TR
ZH
96.101 Confirm user pass code
10000000…99999999
-
-
96.102 User lock functionality
0000h…FFFFh
-
0000h
97 Motor control
97.01 Switching frequency reference
2 kHz[2], 4 kHz[4], 8 kHz[8],
16 kHz[16]
-
4 kHz[4]
97.02 Minimum switching frequency
1, 2, 4, 8, 12
-
1.5 kHz[1]
97.13 IR compensation
0.00...50.00
%
3.50
97.20 U/F ratio
Linear[0], Squared[20]
-
Linear[0]
97.49 Slip gain for scalar
0...200
%
0
97.94 IR comp max frequency
1.0...200.0
%
50.0
98 User motor parameters
98.01
User motor model mode
Not selected[0], Motor
parameters[1]
-
Not
selected[0]
98.02 Rs user
0.00000…0.50000
p.u.
0.00000 p.u
98.03 Rr user
0.00000…0.50000
p.u.
0.00000 p.u
98.04 Lm user
0.00000…10.00000
p.u.
0.00000 p.u
98.05 SigmaL user
0.00000…1.00000
p.u.
0.00000 p.u
98.06 Ld user
0.00000…10.00000
p.u.
100000 = 1
p.u.
98.07 Lq user
0.00000…10.00000
p.u.
100000 = 1
p.u.
98.08 PM flux user
0.00000…2.00000
p.u.
100000 = 1
p.u.
98.09 Rs user SI
0.00000…100.00000
ohm
0.00000 ohm
98.10 Rr user SI
0.00000…100.00000
ohm
0.00000 ohm
98.11 Lm user SI
0.00…100000.00
mH
0.00 mH
98.12 SigmaL user SI
0.00…100000.00
mH
0.00 mH
98.13 Ld user SI
0.00…100000.00
mH
0.00
98.14 Lq user SI
0.00…100000.00
mH
0.00
99 Motor data
99.03 Motor type
Asynchronous motor[0],
Permanent magnet motor[1]
-
Asynchronous
motor[0]
99.04 Motor control mode
Vector[0], Scalar[1]
-
Scalar[1]
99.06 Motor nominal current
0.0...5.2
A
1.8
99.07 Motor nominal voltage
69.2...830.0
V
400.0
99.08 Motor nominal frequency
0.00…500.00
Hz
50.00
99.09 Motor nominal speed
0…30000
rpm
1430
99.10 Motor nominal power
0...10,000
kW or hp
0.75
99.11 Motor nominal cos?
0.00 … 1.00
-
0.00
99.12 Motor nominal torque
0.000…4000000.000 N·m or
0.000…2950248.597 lb·ft
N·m
0.000
99.13 ID run requested
0...3, 5, 6
-
None[0]
99.14 Last ID run performed
See parameter
-
None[0]
Index
Name
Range/List
Unit
Default
1.5 kHz[1]
2 kHz[2]
4 kHz[4]
8 kHz[8]
12 kHz[12]
None[0]
Reduced[2] Autophasing[4]
Advanced[6]
Normal[1] Standstill[3] Current measurement calibration[5]
Adaptive[7]
Note:
Adaptive ID run is applicable for R0...R5 frames and Advanced ID run is applicable for
R6...R8 frames.
ACQ80R0-R8 QIG.book Page 50 Friday, February 1, 2019 1:18 PM
Содержание ACQ80-04 Series
Страница 28: ...28 Start up and use EN ES FI FR IT PL PT RU SV TR ZH ACQ80R0 R8 QIG book Page 28 Friday February 1 2019 1 18 PM...
Страница 52: ...52 Parameters List EN ES FI FR IT PL PT RU SV TR ZH ACQ80R0 R8 QIG book Page 52 Friday February 1 2019 1 18 PM...
Страница 72: ...70 Diagnostics EN ES FI FR IT PL PT RU SV TR ZH ACQ80R0 R8 QIG book Page 70 Friday February 1 2019 1 18 PM...