Program features 39
External control
When the drive is in external control, control commands are given through
• the I/O terminals (digital and analog inputs), or optional I/O extension modules
• the fieldbus interface (via the embedded fieldbus interface or an optional fieldbus
adapter module).
Two external control locations, EXT1 and EXT2, are available. The user can select
the sources of the start and stop commands separately for each location by setting
parameters
. The operating mode can be selected separately for each
location, which enables quick switching between different operating modes, for
example speed and process PID control. Selection between EXT1 and EXT2 is done
via any binary source such as a digital input or fieldbus control word (parameter
). The source of reference is selectable for each operating mode
separately.
Communication fail functionality
The communication fail functionality ensures continuous process without
interruptions. If there is a communication loss, the drive automatically changes the
control location from EXT1 to EXT2. This enables process to be controlled, for
example, with the drive PID controller. When the original control location recovers,
the drive automatically switches control back to the communication network (EXT1).
Settings
• Parameters
(page
);
…
).
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...