148 Parameters
Automatic
Automatic start guarantees optimal motor start in most cases.
It includes the flying start function (starting into a rotating
motor) and the automatic restart function. The drive motor
control program identifies the flux as well as the mechanical
state of the motor and starts the motor instantly under all
conditions.
Note:
If parameter
is set to
,
no flying start or automatic restart is possible unless
parameter
is set to
2
Defines the pre-magnetization time when
• parameter
is set to
(in vector
motor control mode), or
• parameter
(in
scalar motor control mode).
After the start command, the drive automatically
premagnetizes the motor for the set time. To ensure full
magnetizing, set this parameter to the same value as, or
higher than, the rotor time constant. If not known, use the
rule-of-thumb value given in the table below:
Note:
This parameter cannot be changed while the drive is
running.
500 ms
0…10000 ms
Constant DC magnetizing time.
1 = 1 ms
Selects the way the motor is stopped when a stop command
is received.
Additional braking is possible by selecting flux braking (see
parameter
).
Coast
Stop by switching off the output semiconductors of the drive.
The motor coasts to a stop.
WARNING!
If a mechanical brake is used, ensure it is
safe to stop the drive by coasting.
0
Ramp
Stop along the active deceleration ramp. See parameter
group
on page
on page
.
1
Torque limit
Stop according to torque limits (parameters
).
This mode is only possible in vector motor control mode.
2
No.
Name/Value
Description
Def/FbEq16
Motor rated power
Constant magnetizing time
< 1 kW
1 to 10 kW
> 100 to 200 ms
10 to 200 kW
> 200 to 1000 ms
200 to 1000 kW
> 1000 to 2000 ms
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...