Parameters 109
Diagnostic word 3. For possible causes and remedies, see
chapter
-
0000h…FFFFh
Diagnostic word 3.
1 = 1
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Value
0
Main circuit pwr
ON
Yes = Main circuit power is on.
1
Ext. pwr supply
Yes = Control board is powered on from external power supply, for
example, user provided 24 V.
2
Programming
wand
Yes = Control board is powered on by the Programming wand tool
for offline programming or parameterization. Main circuit / power unit
is without power.
3
Panel port comm
loss
Yes = Panel port communication lost.
4
Reserved
5
Field bus force trip Yes = Fault trip forced (requested) from a field bus.
6
Start inhibited
Yes = Start inhibited (prevented) due to some reason for example
interlock.
7
Safe Torq Off
Yes = Safe Torque Off fault active.
8
STO broken
Yes = Safe Torque Off circuitry is broken.
9
kWh pulse
Yes = kWh pulse is active.
10
Reserved
11
Fan command
On = Drive fan is rotating above idle speed.
12…15 Reserved
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...