ACQ550-U1 User’s Manual
247
Fieldbus adapter
Actual Value
As described earlier in section
on page
, Actual Values are
words containing drive values.
Actual Value scaling
The scaling of the integers sent to the fieldbus as Actual Values depends on the
resolution of the selected drive parameter. Except as noted for
ACT
1 and
ACT
2 below,
scale the feedback integer using the resolution listed for the parameter in section
Data words 5 and 6 are scaled as follows:
Virtual addresses of the drive control
The virtual address area of the drive control is allocated as follows:
Feedback integer
Parameter resolution
Scaled Value
1
0.1 mA
1 · 0.1 mA = 0.1 mA
10
0.1%
10 · 0.1% = 1%
ABB Drives profile
Contents
Scaling
ACT
1
ACTUAL
SPEED
-20000 … +20000 = -(par. 1105) … +(par. 1105)
ACT
2
TORQUE
-10000 … +10000 = -100% … +100%
1
Control Word
2
Reference 1 (REF
1)
3
Reference 2 (REF
2)
4
Status Word
5
Actual Value 1 (ACT
1)
6
Actual Value 2 (ACT
2)
Содержание ACQ550-x1-06A6-2
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...