ACQ550-CC Packaged Drive with Bypass
15
Installation
Auto Start Contact
To start the ACQ550 by means of an external un-powered contact (maintained),
connect the contact to 1TB:9 and 1TB:10. Closing this contact will start the motor
when the drive is in the AUTO mode.
Relay Contact Output
A “Motor Running” relay contact output is provided at terminals 1TB:13 and 1TB:14
for external indication of the motor status. The output consists of a normally open
auxiliary contact on the bypass contactor and a normally open “Drive Running”
contact from the ACQ550. The two contacts are connected in parallel so that a
contact closure is provided whenever the motor is running.
Refer to “Control Connections” in the
ACQ550-U1 User’s Manual
Technical Data
where relay contacts are used to control inductive loads.