ACQ550-U1 User’s Manual
87
0136
COMM VALUE 2
Free data location that can be written from serial link.
0137
PROCESS VAR 1
Process variable 1
• Defined by parameters in
.
0138
PROCESS VAR 2
Process variable 2
• Defined by parameters in
.
0139
PROCESS VAR 3
Process variable 3
• Defined by parameters in
.
0140
RUN TIME
The drive’s accumulated running time in thousands of hours (kh).
• Cannot be reset.
0141
MWH COUNTER
The drive’s accumulated power consumption in megawatt hours.
• The counter value is accumulated till it reaches 65535 after which the counter rolls over and starts again from 0.
• Cannot be reset.
0142
REVOLUTION CNTR
The motor’s accumulated revolutions in millions of revolutions.
• Can be reset by pressing UP and DOWN keys simultaneously when the control panel is in the Parameters mode.
0143
DRIVE ON TIME HI
The drive’s accumulated power-on time in days.
• Cannot be reset.
0144
DRIVE ON TIME LO
The drive’s accumulated power-on time in 2 second ticks (30 ticks = 60 seconds).
• Shown in format hh.mm.ss.
• Cannot be reset.
0145
MOTOR TEMP
Motor temperature in degrees Celsius / PTC resistance in ohms.
• Applies only if motor temperature sensor is set up.
• See parameter 3501.
0150
CB TEMP
Temperature of the drive control board in degrees Celsius.
0153
MOT THERM STRESS
Estimated rise of the motor temperature. Value equals to the estimated motor thermal stress as a percentage of the
motor temperature trip level.
0158
PID COMM VALUE 1
Data received from fieldbus for PID control (PID1 and PID2).
0159
PID COMM VALUE 2
Data received from fieldbus for PID control (PID1 and PID2).
0174
SAVED KWH
Energy saved in kWh compared to the energy used when the pump is connected directly to the supply. See the note
on page
• The counter value is accumulated till it reaches 999.9 after which the counter rolls over and starts again from 0.0.
• Can be reset with parameter 4509
ENERGY
RESET
(resets all energy calculators at the same time).
0175
SAVED MWH
Energy saved in MWh compared to the energy used when the pump is connected directly to the supply. See the note
on page
• The counter value is accumulated till it reaches 65535 after which the counter rolls over and starts again from 0.
• Can be reset with parameter 4509
ENERGY
RESET
(resets all energy calculators at the same time).
Code Description
Содержание ACQ550-U1-011A-6
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...