ACQ550-U1 User’s Manual
35
Start-up, control with I/O and ID Run
How to perform the limited start-up
Before you start, ensure that you have the motor nameplate data on hand.
SAFETY
The start-up may only be carried out by a qualified electrician.
The safety instructions given in chapter
must be followed during the start-up
procedure.
The drive will start up automatically at power up, if the external run command is on.
Check the installation. See the checklist in chapter
Check that the starting of the motor does not cause any danger.
De-couple the driven machine
if:
• there is a risk of damage in case of incorrect direction of rotation, or
• an ID Run can be performed during the drive start-up. ID Run is essential only in
applications that require the ultimate in motor control accuracy.
POWER-UP
Apply input power.
Select MENU to enter the main menu.
Select the Parameters mode with keys
/
and select
ENTER to select the Parameters mode.
Select the Start-Up Data group with keys
/
and
select SEL.
Select the application macro (parameter
) with keys
/
. Select EDIT to change the parameter value. The default
value 6 (
PID
CONTROL
) is suitable in most cases for pumping.
Press keys
/
to change the parameter value.
Select SAVE to store the modified value or select CANCEL to
leave the set mode. Any modifications not saved are cancelled.
PID CONTROL
PID CONTROL
Содержание ACQ550-U1-011A-6
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...