24
ACQ550-U1 User’s Manual
Installation
Control terminals table
The following provides information for connecting control wiring at X1 on the drive.
X1
Hardware description
1
SCR
Terminal for signal cable shield (screen). (Connected internally to chassis ground.)
2
AI1
Analog input channel 1, programmable. Default
2
= frequency reference. Resolution
0.1%, accuracy ±1%.
Two different DIP switch types can be used.
J1: AI1 OFF: 0…10 V (
R
i
= 312 kohm)
J1: AI1 ON: 0…20 mA (
R
i
= 100 ohm)
3
AGND
Analog input circuit common (connected internally to chassis gnd. through 1 Mohm).
4
+10 V
Potentiometer reference source: 10 V ±2%, max. 10 mA (1 kohm <
R
< 10 kohm).
5
AI2
Analog input channel 2, programmable. Default
2
= not used. Resolution 0.1%,
accuracy ±1%.
Two different DIP switch types can be used.
J1: AI2 OFF: 0…10 V (
R
i
= 312 kohm)
J1: AI2 ON: 0…20 mA (
R
i
= 100 ohm)
6
AGND
Analog input circuit common (connected internally to chassis gnd. through 1 Mohm).
7
AO1
Analog output, programmable. Default
2
= frequency. 0…20 mA (load < 500 ohm).
Accuracy ±3%.
8
AO2
Analog output, programmable. Default
2
= current. 0…20 mA (load < 500 ohm).
Accuracy ±3%.
9
AGND
Analog output circuit common (connected internally to chassis gnd. through 1 Mohm).
10 +24V
Auxiliary voltage output 24 V DC / 250 mA (reference to GND), short circuit
protected.
11
GND
Auxiliary voltage output common (connected internally as floating).
12 DCOM
Digital input common. To activate a digital input, there must be
10 V
(or
-10 V) between that input and DCOM. The 24 V may be provided by the
ACQ550 (X1-10) or by an external 12…24 V source of either polarity.
13 DI1
Digital input 1, programmable. Default
2
= start/stop.
14 DI2
Digital input 2, programmable. Default
2
= fwd/rev.
15 DI3
Digital input 3, programmable. Default
2
= constant speed sel (code).
16 DI4
Digital input 4, programmable. Default
2
= constant speed sel (code).
17 DI5
Digital input 5, programmable. Default
2
= ramp pair selection (code).
18 DI6
Digital input 6, programmable. Default
2
= not used.
Analog I/O
ON
1
ON
ON
1
ON
ON
1
ON
ON
1
ON
Digit
a
l input
s
1
Содержание ACQ550-U1-011A-6
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...