190
ACQ550-U1 User’s Manual
Embedded fieldbus
Feedback from the drive – EFB
Pre-defined feedback
Inputs to the controller (drive outputs) have pre-defined meanings established by the
protocol. This feedback does not require drive configuration. The following table lists
a sample of feedback data. For a complete listing, see input word/point/object
listings in the technical data for the appropriate protocol starting on page
Note:
With Modbus, any parameter can be accessed using the format: 4 followed by
the parameter number.
Mailbox read/write
The ACQ550 provides a “Mailbox” function to access parameters that have not been
pre-defined by the protocol. Using mailbox, any drive parameter can be identified
and read. Mailbox can also be used to adjust parameter settings by writing a value to
any parameter identified. The following table describes the use of this function.
1. As noted above, Modbus provides direct access to all parameters using the format: 4 followed by
the parameter number.
Drive Parameter
Protocol Reference
Modbus
BACnet
0102
SPEED
40102
AV0
0103
FREQ OUTPUT
40103
AV1
0104
CURRENT
40104
AV4
0105
TORQUE
40105
AV5
0106
POWER
40106
AV6
0107
DC BUS VOLT
40107
AV2
0109
OUTPUT VOLTAGE
40109
AV3
0115
KWH COUNTER
40115
AV8
0118
DI1-3 STATUS – bit 1 (DI3)
40118
BI6, BI7, BI8
0122
RO1-3 STATUS
40122
BI0, BI1, BI2
0301
FB STATUS WORD – bit 0 (STOP)
40301 bit 0
BV0
0301
FB STATUS WORD – bit 2 (REV)
40301 bit 2
BV1
Name
Description
Protocol Reference
Modbus
1
BACnet
Mailbox
Parameter
Enter the number of the drive parameter to
access.
Does not apply.
AV25
Mailbox
Data
Contains the parameter value after a read, or
enter the desired parameter value for a write.
AV26
Mailbox
Read
A binary value triggers a read – the value of the
“Mailbox Parameter” appears in “Mailbox data”.
BV15
Mailbox
Write
A binary value triggers a write – the drive value
for the “Mailbox Parameter” changes to the value
in “Mailbox data”.
BV16
Содержание ACQ550-U1-011A-6
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...