Group 31: AUTOMATIC RESET
This group defines conditions for automatic resets. An automatic reset occurs after a
particular fault is detected. The drive holds for a set delay time, then automatically
restarts. You can limit the number of resets in a specified time period and set up
automatic resets for a variety of faults.
Code Description
3101
NUMBER OF TRIALS
Sets the number of allowed automatic resets within a trial period defined
by 3102
TRIAL
TIME
.
• If the number of automatic resets exceeds this limit (within the trial
time), the drive prevents additional automatic resets and remains
stopped.
• Starting then requires a successful reset performed from the control
panel or from a source selected by 1604
FAULT
RESET
SEL
.
Example:
Three faults have occurred in
the trial time. The last is reset only if the
value for 3101
NUMBER
OF
TRIALS
is 3 or
more.
3102
TRIAL TIME
Sets the time period used for counting and limiting the number of resets.
• See 3101
NUMBER
OF
TRIALS
.
3103
DELAY TIME
Sets the delay time between a fault detection and attempted drive restart.
• If
DELAY
TIME
= zero, the drive resets immediately.
3104
AR OVERCURRENT
Sets the automatic reset for the overcurrent function on or off.
0 =
DISABLE
– Disables automatic reset.
1 =
ENABLE
– Enables automatic reset.
• Automatically resets the fault (
OVERCURRENT
) after the delay set by 3103
DELAY
TIME
, and the drive resumes
normal operation.
3105
AR OVERVOLTAGE
Sets the automatic reset for the overvoltage function on or off.
0 =
DISABLE
– Disables automatic reset.
1 =
ENABLE
– Enables automatic reset.
• Automatically resets the fault (
DC
OVERVOLT
) after the delay set by 3103
DELAY
TIME
, and the drive resumes
normal operation.
3106
AR UNDERVOLTAGE
Sets the automatic reset for the undervoltage function on or off.
0 =
DISABLE
– Disables automatic reset.
1 =
ENABLE
– Enables automatic reset.
• Automatically resets the fault (
DC
UNDERVOLT
) after the delay set by 3103
DELAY
TIME
, and the drive resumes
normal operation.
3107
AR AI<MIN
Sets the automatic reset for the analog input less than minimum value function on or off.
0 =
DISABLE
– Disables automatic reset.
1 =
ENABLE
– Enables automatic reset.
• Automatically resets the fault (
AI
<
MIN
) after the delay set by 3103
DELAY
TIME
, and the drive resumes normal
operation.
WARNING!
When the analog input signal is restored, the drive may restart, even after a long stop. Make
sure that automatic, long delayed starts will not cause physical injury and/or damage equipment.
3108
AR EXTERNAL FLT
Sets the automatic reset for external faults function on or off.
0 =
DISABLE
– Disables automatic reset.
1 =
ENABLE
– Enables automatic reset.
• Automatically resets the fault (
EXT
FAULT
1 or
EXT
FAULT
2) after the delay set by 3103
DELAY
TIME
, and the drive
resumes normal operation.
X
X X
Time
Trial time
x = Automatic reset
Содержание ACQ550-U1-011A-6
Страница 1: ...ACQ550 User s Manual ACQ550 U1 Drives 1 200 hp ...
Страница 4: ......
Страница 10: ...10 ACS550 U1 User s Manual Table of contents ...
Страница 42: ...42 ACQ550 U1 User s Manual Start up control with I O and ID Run ...
Страница 56: ...56 ACQ550 U1 User s Manual Control panel ...
Страница 68: ...68 ACQ550 U1 User s Manual Application macros ...
Страница 250: ...250 ACQ550 U1 User s Manual Fieldbus adapter ...
Страница 266: ...266 ACQ550 U1 User s Manual Maintenance ...
Страница 314: ...314 ACQ550 U1 User s Manual Index ...