16 Safety instructions
Additional instructions and notes
WARNING!
Obey these instructions. If you ignore them, injury or death, or
damage to the equipment can occur.
•If a drive whose varistors are not disconnected is installed on an IT power
system (an ungrounded power system or a high resistance grounded [over 30
ohms] power system), the drive will be connected to earth potential through the
varistors. This may cause danger or damage the drive.
• If a drive whose varistors (built-in) or mains filter (external option) are not
disconnected is installed on an corner-grounded TN system, the drive will be
damaged.
• Use all ELV (extra low voltage) circuits connected to the drive only within a zone
of equipotential bonding, that is, within a zone where all simultaneously
accessible conductive parts are electrically connected to prevent hazardous
voltages appearing between them. You can accomplish this by a proper factory
grounding, that is, make sure that all simultaneously accessible conductive parts
are grounded to the protective earth (PE) bus of the building.
• Do not do insulation or voltage withstand tests on the drive or drive modules.
Note:
• The motor cable terminals of the drive are at a dangerous voltage when the input
power is on, regardless of whether the motor is running or not.
• The DC and brake resistor terminals (UDC+, UDC-, R+ and R-) are at a
dangerous voltage.
• External wiring can supply dangerous voltages to the terminals of relay outputs.
• The Safe torque off function does not remove the voltage from the main and
auxiliary circuits. The function is not effective against deliberate sabotage or
misuse.
WARNING!
Use a grounding wrist band when you handle the printed circuit
boards. Do not touch the boards unnecessarily. The components on the
boards are sensitive to electrostatic discharge.
Содержание ACL30
Страница 1: ...ABB high performance elevator drives User s manual ACL30 elevator drive ...
Страница 4: ......
Страница 20: ...20 Safety instructions ...
Страница 34: ...34 Operation principle and hardware description ...
Страница 42: ...42 Planning the cabinet installation ...
Страница 60: ...60 Planning the electrical installation ...
Страница 126: ...126 Using the control panel ...
Страница 318: ...318 Maintenance ...
Страница 334: ...334 The Safe torque off function ...
Страница 338: ...338 Mains chokes ...
Страница 342: ...342 EMC filters ...
Страница 348: ...Dimension drawings 348 Frame size B D1 D2 W H1 H2 ...
Страница 349: ...Dimension drawings 349 ...
Страница 350: ...Dimension drawings 350 Frame size C D1 D2 H2 H1 W ...
Страница 351: ...Dimension drawings 351 ...
Страница 352: ...Dimension drawings 352 Frame size D ...
Страница 354: ...354 Dimension drawings EMC filters JFI 0x ...
Страница 356: ...356 Dimension drawings Brake resistors JBR xx ...
Страница 358: ...358 Dimension drawings ...
Страница 360: ...Contact us www abb com drives www abb com drivespartners 3AXD50000036355 Rev B EN EFFECTIVE 2016 11 21 ...